Heat exchangers provide cool relief

Neal Collier -- Control Engineering, 7/1/2000

Editor's note: 'Integrator Update' is an occasional department examining an application from a system integrator's viewpoint.

Total Systems Design (TSD) (Exton, Pa.) recently integrated the controls for a Basic Oxygen Furnace (BOF) Hood Cooling System at Bethlehem Steel Corp.'s Sparrows Point facility.

The system is a PLC-controlled, closed-loop, cooling water system. In the system, the heat generated is removed from the water through use of air-cooled Heat Exchangers (HEXs); each having a set of two variable-frequency drive (VFD) fans. Each Oxygen Furnace batch (Heat) lasts about 25 minutes. During the Heat, the temperature rises from a minimum to a maximum, achieves steady state, and then drops back to the minimum.

Ten HEXs are available for use in the system. Six or eight are placed in Automatic, with one in Standby. Each HEX can be isolated from the system through use of an inlet isolation valve. When a HEX is on line (in Automatic), the valve is open and the fan speeds are controlled by the PLC. Although HEXs may be on line with water flowing through them, if the temperature is low enough, the HEX fans may not be running. The first image shows a view from beneath a HEX fan.

A feed-forward scheme is used to calculate the HEX fan speeds based on the heat to be removed, the number of HEXs in Automatic, HEX air inlet temperature, and HEX fouling factor. The original system design had the HEX VFDs restricted to an operating range of 10-100% of rated speed (e.g., <10% rated speed, speed set to zero). Using this scheme, the fans (for the HEXs in Automatic) effectively start and stop as a bank.

Delay compensation

One problem encountered was that the heat source is in a separate building several hundred yards from the HEXs. When the water temperature changes at the heat source, it takes approximately 60 seconds for this change to reach the HEXs. To prevent problems with cooling, the fan speed signal had to be delayed to allow the change in speed to occur the same time the temperature change reaches the HEXs.

A sub-routine was created to delay each calculated speed signal and send it to the individual fan set control files, which then make the determination whether or not to 'allow' the speed signal to pass to the VFD (e.g., in Automatic, >10%). The delay method developed was extremely helpful during Site Acceptance Testing because the delay could be changed to fine-tune the system response. The delay sub-routine also allows standby HEX to be brought on line with the fans at (or near) the correct (and delayed) speed.

During commissioning, the VFD OEM informed the project team that the VFDs were restricted to an operating range of 25-100%. The program was changed and commissioning successfully completed. With the HEX fans starting and stopping as a bank, residual heat was being built up in the heat source before the calculated speed rose above 25% and remained at the end of a Heat once the speed dropped below 25%.

Residual heat

The residual heat created significant hot spots in the cooling panels that remove the heat from the heat source. These hot spots were shortening the life of the equipment, and created the potential for material failure (and plant shutdown).

A post-commissioning modification to start and stop HEX fan sets sequentially, rather than starting or stopping the fan sets as a bank solved the hot-spot problem. This modification was implemented with no loss of production time. Once implemented, the sequential (versus bank) starting and stopping of fan sets lowered the cooling panel temperatures by up to 20 °F.

Integrator: Total Systems Design, Exton, Pa., www.totalsystemsdesign.com (contact Neal Collier), is a member of the Control System Integrator Association, www.controlsys.org.

For more information, visit www.controleng.com/freeinfo.

Email
Print
Reprint
Learn RSS

Talkback

We would love your feedback!

Post a comment

» VIEW ALL TALKBACK THREADS

Related Content

Related Content

 

By This Author

There are no other articles written by this author.

Sponsored Links

 

Advertisement
SPONSORED LINKS

More Content

  • Blogs
  • Discussions
  • Webcasts
  • Podcasts
  • Videos

Blogs

  • David Chappell
    Standard profits: Make2Pack and ISA88

    December 31, 2008
    Best of Standard profits: Make2Pack and ISA88 blog for 2008; how cold is minus 40 degrees?
    I have had time to look back on the events of the past two years while here in North Pole Alaska (see the very cold photos at the bottom of the pos......
    More
  • Charlie Masi
    Ask Charlie

    December 29, 2008
    How do 10X oscilloscope probes work?
    Oscilloscopes are probably the most useful, and most used of general-purpose electronic test instruments. In the hands of a knowledgeable test engi......
    More
  • View All BlogsRSS

Webcasts

Engineering-driven Ethernet
This Control Engineering Roundtable Webcast will address the engineering issues you should be aware of when exploring the adoption of Ethernet or when looking to expand its use in your facility.

Bridging gaps with wireless
Discover how you can create stronger, flexible and cost-effective wireless connections for your entire plant. Register today!

View All Webcasts

Podcasts

Integration platforms such as EDDL and FDT/DTM help integrate increasingly intelligent instrumentation and devices with control and asset management systems. This audio tutorial helps you understand how these platforms operate and what they can do.
Integration Platforms: EDDL and FDT/DTM
Integration platforms such as EDDL and FDT/DTM help integrate increasingly intelligent instrumentation and devices with control and asset management systems. This audio tutorial helps you understand how these platforms operate and what they can do. Hear It Now

View All Podcasts Subscribe Now to Process Control & Instrumentation and never miss an episode
Advertisements





NEWSLETTERS

Get engineering industry news, trends, and business-critical information delivered directly to your inbox!

Click on a title below to learn more.

Weekly News (Weekly)
Process Instrumentation & Sensors (Monthly)
System Integration Monthly (Monthly)
Process & Advanced Control (Monthly)
Machine Control (Monthly)
Information Control (Monthly)
Automation Control (Monthly)
Product Review (Monthly)
Sustainable Engineering (Monthly)
Simplified Safety
Fieldbus Facts
PROFInews North American Edition
About Us   |   Advertising Info   |   Site Map   |   Contact Us   |   Useful Sites   |   FREE Subscription   |   RSS
© 2009 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites