System Error Budgets, Accuracy, Resolution

Designing any automation system requires clear understanding of error and resolution. Here are key points for review.

By Staff -- Control Engineering, 10/1/2005

AT A GLANCE
  • Accuracy, resolution
  • Error budget
  • Sources of error tables
  • Tutorial, examples graphs

Any system design requires development and analysis of system error budgets. System engineers must determine the necessary levels of accuracy for system elements, including field sensors, actuators, signal conditioning modules (SCMs), and controlling units (PCs and PLCs). In addition, error budget considerations need to include software algorithm integrity and operating system compatibility, or the degree of software 'openness.'

For example, accuracy and resolution of software algorithm calculations must be compatible with measurement accuracy. When analyzing system accuracy needs, the topic of resolution requires attention as it relates to overall accuracy. Often, distinguishing between accuracy and resolution is misinterpreted in determining system needs. While accuracy and resolution are related, significant differences exist.

A reading device that has a specified accuracy of ±0.015% actually will give a reading between 0.99985 and 1.00015 times the actual value. While this is considered a measure of accuracy, it's interesting to note that the ±0.015% number is, in reality, the 'error.'

Accuracy is the measurement device's degree of absolute correctness, whereas resolution is the smallest number that can be displayed or recorded by the measurement device. For example, measuring 1 volt within ±0.015% accuracy requires a 6-digit instrument capable of displaying five decimal places. The fifth decimal place represents 10 microvolts, giving this instrument a resolution of 10 microvolts.

For the following examples, the digital display quantizing error (±1 bit minimum) in the least significant digit is assumed to be zero.

Is it accurate? It depends

Suppose a voltage source is known to be exactly 5.643 volts. Now imagine using a digital voltmeter that is 100% accurate, but has only three display digits and is defined as '3-digit resolution.' The reading would be 5.64 volts. Is the reading accurate? There was an accurate source and an accurate voltmeter, yet the reading does not represent the actual voltage value. Some may say that our 100% accurate voltmeter gave us a reading error of 3 millivolt or 0.0532%. The reading could be considered in error unless only a 3-digit reading is desired. In cases where source and instrument accuracy are 100%, resolution of the reading instrument and the acceptance of the observer determine what constitutes 'accuracy.'

Assume a 100% accurate source of 5.643 volts, but in this case the 3-digit display digital voltmeter has a ±0.015% accuracy specification (meaning the displayed value is between 0.99985 and 1.00015 times the source value). In this case, the digital voltmeter still reads 5.64 volts, which is to say that this 0.015% accurate instrument gives a 0.0532% error, same as the first example. Once again, the resolution and the observer determine what constitutes 'accuracy.'

Next, consider measuring the precise 5.643-volt source using a 5-digit display digital voltmeter with a specified accuracy of ±0.015%. This instrument displays a reading of between 5.6421 (for 5.64215) and 5.6438 (for 5.64385).

Machine Control

Taking the same measurement using a 6-digit display digital voltmeter, again, with a specified accuracy of ±0.015%, the display will be between 5.64215 and 5.64385.

Clearly, these examples show the relation between accuracy and resolution and how each situation has to be evaluated based on the system requirements and the observer's acceptance of 'error.'

Typically, sensor signals are conditioned with signal conditioning modules (SCMs), selected, and then converted into a usable number, either for analytical process control or observation.

In the graphic 'Typical instrumentation signal flow,' assume sensors have ±0.25% (E1) accuracy specifications, SCMs have ±0.03% (E2) accuracy specifications, and the select-converter function has ±0.05% (E3) net accuracy. The table below the graphic displays some different system 'accuracy' correction calculations. Since errors are random and have ± values, RMS (root-mean-square) calculations are often used as opposed to the worst case maximum and minimum. RMS error is defined as the square root of the sum of each error squared, {(E1)2 + (E2)2 + (E3)2}.

Number values from the converter function are presented to the observer with a display unit that has its own error and resolution specifications. In addition, the analytical processing function imports this numerical value to use in a complex mathematical operation, which may be based on an empirical model that achieves results using computation shortcuts, which, in turn, have additional accuracy and resolution specifications. A detail error budget must, therefore, contain numerous factors to correctly determine 'system accuracy.'

Machine Control
Resolution isn't accuracy

Suppose your project manager drops by, makes small talk about how the control system project is going, then asks if you and your team have any needs. Before leaving, he comments that while reviewing project purchases he noticed that the analog-to-digital converter (ADC) module for the main controller is an 8-channel differential input unit with 16-bit resolution, which he thought would give one part in (216-1) accuracy, something on the order of 0.0015%. He says he also noticed that all the SCMs you purchased were only 0.03%. Politely, he asks you to explain. You begin your explanation by pictorially representing one possible ADC system, as illustrated in the 'Typical instrumentation signal flow' graphic. ADCs are advertised as having 'n' bit resolution, you mention, which often is misunderstood to mean accuracy.

Specifications do need to be closely examined, however, to determine the unit's accuracy. 'Conceptual ADC system' graphic depicts a typical scheme used to convert an analog signal to a digital representation for computer manipulations or display. In this typical representation, semiconductor switches select analog input signals, which are captured (sampled for a small slice of time) and held in a sample and hold amplifier function block (sample and hold amplifier; SHA). This SHA function may also contain a programmable gain function to selectively scale each analog input. Once a signal slice is captured, an n-bit counter begins counting.

Counter contents are converted to an analog voltage using switched resistors or current sources. When this analog signal equals the input SHA signal, counting halts and the counter contents are made available as a digital representation of the sampled analog input value. This process can sample analog inputs at blinding speeds in the 10-MHz range to provide digital representations of time-varying analog inputs; it also has numerous sources of error that collectively degrade true accuracy. It is not necessarily determined solely by the n-bit resolution specification.

Here are five errors associated with using a typical ADC scheme as illustrated:

  1. Sampling speed. From Nyquist Sampling Theory, if the analog signal changes rapidly, then the ADC must sample at least twice as fast as the changing input. Many applications use a sampling rate at least 10 times the highest frequency present in the input signal. Sampling slower than one-half the signal frequency will result in inaccurate readings. Most ADC sampling speeds are adequate for slow varying process control signals.
  2. Input multiplexed errors. The input multiplexer circuit may have OpAmp buffers on each input line that could introduce errors, such as in voltage offset, current bias, and linearity. In addition (and more common) are the two major multiplexer errors: (a) cross talk between channels, that is, the signal from an 'on' channel leaks current into the 'off' channels, and (b) signal reduction through voltage division caused by the finite non-zero resistance of the semiconductor switches and the finite input impedance of the circuitry that follows.
  3. Sample and hold amplifier (SHA). This function is an OpAmp-based circuit with capacitive components all designed to switch, buffer, and hold the sampled analog voltage value. Consequently, there will be linearity, gain, power supply rejection ratio (PSRR), voltage offset, charge injection, and input bias current errors.
  4. Converter. In the counter, comparator, and ADC circuit there are such errors as overall linearity, quantizing error (defined as uncertainty in the least significant bit [LSB], typically ±1/2 LSB), and PSRR.
  5. Temperature. All analog circuit functions within the ADC unit are subject to temperature errors, therefore an overall temperature error specification is assigned to an ADC.

Data for 'Typical 14-bit ADC errors...' table were taken from various analog-to-digital converter manufacturers. This isn't a complete ADC error analysis; values shown illustrate that internal errors collectively contribute to the definition of an ADC's overall accuracy.

An algebraic sum model on these errors suggests a ±0.1% error for this 14-bit ADC, whereas the RMS sum model suggests a ±0.05 % error. Resolution alone erroneously implies ±0.006%. These internal ADC error numbers, used in either an algebraic or RMS summing model, clearly illustrate that the net effective accuracy of an n-bit ADC is not equal to the ADC resolution, defined as approximately 1/(2n-1). To determine actual ADC accuracy, the manufacturer's ADC specifications should always be carefully examined, along with specifications for sensors and SCMs.

For more information, visit www.dataforth.com.

Accuracy calculation table
Method CorrectionPercent
Max: (1+E1)*(1+E2)*(1+E3)* 1.003302150.330215037%
Min: (1-E1)*(1-E2)*(1-E3) * 0.99670215 - 0.329785037
RMS Max: (1+RMS Error) *1.00256710 0.256709953
RMS Min: (1-RMS Error) *0.99743290 - 0.256709953
Source: Control Engineering with information from Dataforth

Typical 14-bit ADC errors: Temperature change 30 °C; ±15 V supply change ± 1%
FunctionCause of ErrorTypical ± error in ppm
MultiplexerCross Leakage0.01 ppm
Switch Resistance0.003
Sample and hold amplifier (S&H)Nonlinearity100
Gain100
PSRR10
Voltage offset80
Bias input current0.08
ConverterPSRR60
Nonlinearity122
Quantizing60
Gain vs. temperature300
Zero vs. temperature300
Source: Control Engineering with information from Dataforth

Email
Print
Reprint
Learn RSS

Talkback

We would love your feedback!

Post a comment

» VIEW ALL TALKBACK THREADS

Related Content

Related Content

 

By This Author

Sponsored Links

 

Advertisement
SPONSORED LINKS

More Content

  • Blogs
  • Discussions
  • Webcasts
  • Podcasts
  • Videos

Blogs

  • Paul Grayson
    AIMing for Automated Vehicles

    November 30, 2008
    Pass In Review
    Photo: AIM photo archive US ARMY M35A2 US Army cargo truck on loan to AMERICAN INDUSTRIAL MAGIC for the DARPA Grand Challenge. The phot......
    More
  • Paul Grayson
    AIMing for Automated Vehicles

    November 29, 2008
    Where To Look
    WORLDS SECOND LARGEST AUTO SHOW Need automotive systems or parts for your driverless vehicle project? Check out the 10-12 December 2008,......
    More
  • View All BlogsRSS

Discussions

  • Re: Modbus Slave Simulator (reply posted by Mark)

  • Magelis XBTGT with Zelio Smart Relay via MODBUS (posted by N1K0)

  • P & I Autocad symbols (posted by Takudzwa)


  • Source: Control.com, the global online discussion community for automation professionals.

    Webcasts

    Engineering-driven Ethernet
    This Control Engineering Roundtable Webcast will address the engineering issues you should be aware of when exploring the adoption of Ethernet or when looking to expand its use in your facility.

    Bridging gaps with wireless
    Discover how you can create stronger, flexible and cost-effective wireless connections for your entire plant. Register today!

    View All Webcasts
    Advertisements





    NEWSLETTERS

    Get engineering industry news, trends, and business-critical information delivered directly to your inbox!

    Click on a title below to learn more.

    Weekly News (Weekly)
    Process Instrumentation & Sensors (Monthly)
    System Integration Monthly (Monthly)
    Process & Advanced Control (Monthly)
    Machine Control (Monthly)
    Information Control (Monthly)
    Automation Control (Monthly)
    Product Review (Monthly)
    Simplified Safety
    Fieldbus Facts
    PROFInews North American Edition
    About Us   |   Advertising Info   |   Site Map   |   Contact Us   |   Useful Sites   |   FREE Subscription   |   RSS
    © 2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
    Use of this Web site is subject to its Terms of Use | Privacy Policy
    Please visit these other Reed Business sites