See the unseen: Power data diagnostics

-- Control Engineering, 6/1/2008

Using reports from relay events can help diagnose power system problems, increase system reliability, lower maintenance costs, and reduce potential for system damage and outages.

Today's microprocessor-based relays collect and save event reports during faults and other problematic conditions. The event report and sequential events recorder (SER) capability of advanced relays enable protection engineers to gain a better understanding of faults and disturbances on transmission line systems through analysis of event reports. This analysis frequently leads to better line parameters, more accurate fault locating for complex faults, and improved understanding of electric power system operations.

Event reports help determine fault resistance and explain otherwise inexplicable events (see graph). They also aid in testing and troubleshooting relay settings and protection schemes that protect costly equipment critical to consumer and industrial services.

Event record detective

The importance of event report records was demonstrated at the city of Conway, AR, 20 miles north of Little Rock. Conway's city-owned power system includes two feeders from its substation, one supplying an industrial customer, and the other supplying the balance of the small city's business and residential customers. Technology from Schweitzer Engineering Laboratories Inc. (SEL) of Pullman, WA, helped detect what might have become a much larger problem.

“The industrial customer had detected what they considered a voltage problem,” says Emery Perry, an SEL field application technician called in to consult on the situation. “Yet when technicians from the Conway Electric Department went to inspect the substation, they noticed that there was no trip on the breaker,” Perry says. The technicians at Conway Electric received training on SEL equipment, enabling them to take advantage of event report records in the SEL relays. In the next step, technicians decided to check the event history in the SEL relays to check for relevant event reports on the feeder in question.

They found that existing event reports seemed to indicate a voltage issue. So they consulted Perry to confirm what seemed to be an unusual problem.

“From the oscillograph readings, it appeared that the problem could be in the source—and in this case the source was a transformer,” Perry says.

Hardware, software involved

Conway Electric Department uses SEL-351S-7 and SEL-351S-6 protection and breaker control relays and SEL-551 overcurrent/reclosing relays in its distribution substations. SEL-351S-7 Relay is used on the feeder main, with the SEL-551 as backup. SEL-351S-6 Relays provide feeder protection and reclosing.

Perry says event records there showed a decrease in C-phase current (IC) and C-phase voltage (VC), while A-phase and B-phase currents increased. “This occurred on two feeders. I suggested testing their transformer, which was a tap changer. When we inspected it, the rotary tap changer contacts were severely worn. [See photo.]

“What was causing the problem was that the C-phase on the utility transformer was opening up, and the industrial customer was in single phase,” Perry says. “It wasn't a complete opening; actually, the moving contacts in the transformer were arcing. That's why the event report oscillograph showed the collapsed C-phase voltage and the collapsed C-phase current, just as if you were removing the voltage off of the load C-phase. There was a three-phase system within the industrial facility that was actually single phasing, which could cause equipment damage. And, of course, the arcing of the transformer caused damage to the contacts.” Although transformers are generally among the most dependable components in an electrical system (failure rates are estimated at a minimal 76 failures per 10,000 years of transformer life), when failures occur, they can result in costly outages, considerable downtime, and expensive replacements, he explains.

Damage avoided

“In this case, I would say that early analyses of the event record helped prevent a possible transformer fire and a sustained power outage, and also possible damage to the industrial plant equipment from a continued single-phasing condition,” Perry says. Each time an SEL relay generates a standard event report, it also generates a corresponding event summary. Event description includes relay/terminal identification; event type, date, and time; fault location; and other information. Event summaries can be viewed using the front-panel LCD or front-panel serial port of the SEL-351S.

Date and time of each transition are available in event reports, downloadable to any PC, he says. The chronology helps technicians determine the order and cause of events so that comprehensive troubleshooting is facilitated. With an appropriate setting, the relay will automatically send an event summary in ASCII text to one or more serial ports each time an event report is triggered.

In addition to storing event summaries and full-length event reports, SEL relays can track the pickup and dropout of protection elements, control inputs, and contact outputs.


For more information...
For more information, go to www.selindustrial.com

Email
Print
Reprint
Learn RSS

Talkback

We would love your feedback!

Post a comment

» VIEW ALL TALKBACK THREADS

Related Content

Related Content

 

By This Author

There are no other articles written by this author.

Sponsored Links

 

Advertisement
SPONSORED LINKS

More Content

  • Blogs
  • Discussions
  • Webcasts
  • Podcasts
  • Videos

Blogs

  • Charlie Masi
    Ask Charlie

    September 29, 2008
    What’s the difference between accuracy and precision?
    Accuracy and precision are used to describe properties of a measurement. The science of making measurements is called metrology. At first, it might......
    More
  • David Chappell
    Standard profits: Make2Pack and ISA88

    September 16, 2008
    Skills gap: Standards, workforce development, and Automation Federation
    Have you heard about Automation Federation efforts on workforce development? Having each vendor responsible for teaching people how to use software......
    More
  • View All BlogsRSS

Webcasts

Engineering-driven Ethernet
This Control Engineering Roundtable Webcast will address the engineering issues you should be aware of when exploring the adoption of Ethernet or when looking to expand its use in your facility.

Bridging gaps with wireless
Discover how you can create stronger, flexible and cost-effective wireless connections for your entire plant. Register today!

View All Webcasts

Podcasts

Control Engineering editorial director David Greenfield conducted a series of interviews on the topic of Ethernet security in the wake of panel discussions on the topic at this year’s Hannover Fair.
Ethernet Security
Control Engineering editorial director David Greenfield conducted a series of interviews on the topic of Ethernet security in the wake of panel discussions on the topic at this year’s Hannover Fair. Hear It Now

View All Podcasts Subscribe Now to Podcasts and never miss an episode
Advertisements





NEWSLETTERS

Get engineering industry news, trends, and business-critical information delivered directly to your inbox!

Click on a title below to learn more.

Weekly News (Weekly)
Process Instrumentation & Sensors (Monthly)
System Integration Monthly (Monthly)
Process & Advanced Control (Monthly)
Machine Control Monthly (Monthly)
Information Control (Monthly)
Automation Control (Monthly)
Product Review (Monthly)
Simplified Safety (Monthly)
Fieldbus Facts (Monthly)
PROFInews North American Edition (Monthly)
About Us   |   Advertising Info   |   Site Map   |   Contact Us   |   Useful Sites   |   FREE Subscription   |   RSS
© 2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites