Guided wave radar increases plant availability, reduces energy costs

Improved level measurement increases availability of condensate receiver.

06/27/2011


Emerson’s Rosemount 5301 Guided Wave Radar with Rosemount 9901 Chamber, prior to adding insulation. Courtesy: Emerson Process ManagementAbsolute Energy LLC has installed Emerson’s Rosemount guided wave radar (GWR) and chamber technology to monitor the water level in a condensate receiver for a sieve dehydration process at its ethanol production facility near Lyle, Minn. Replacing the plant’s existing level transmitters, the new equipment has reportedly helped avoid shutdowns that can cost as much as $20,000 an hour in lost production and potential equipment damage costing over $200,000.

“Our condensate receiver levels went from being a constant headache to being hardly noticeable because the GWR is so reliable,” said Travis Rosenberg, Maintenance Manager, Absolute Energy. “The increased reliability has helped us to lower the risk of equipment damage, increase plant availability, decrease energy and utilities costs and reduce maintenance costs.”

The 115 million gallon per year plant identified a way of improving operations by increasing the reliability and availability of the condensate receiver tank on the steam heat exchanger. The availability of the condensate receiver is critical to continuous operation of the heat exchanger and molecular sieve dehydration process. If water levels get too high in the receiver, temperatures in the heat exchanger drop, which can cause wet ethanol to enter the molecular sieve beds. This forces the process to be shut down and the ethanol-water mixture to be reprocessed.

Previously the level measurement was performed by DP transmitters mounted on wet legs. Excursions from high vacuum to low pressure in the condenser make it challenging for DP technology to monitor the levels in the tank reliably.

3-in diameter Rosemount 9901 Chamber after adding insulation. Courtesy: Emerson Process ManagementThe pressure changes can cause the fill heights in the wet legs to vary widely, making it difficult to get a reading during startup and providing errors in accuracy of as much as 20%. Also DP technology is affected by density changes of the measured fluid, which impacts the accuracy as well.

The unreliable level measurements affected operations. When the condensate levels got too high, the upset led to a molecular sieve dehydration process shutdown – which can cost as much as $20,000 in lost production per hour. If temperatures drop in the heat exchanger and the upset occurs before the wet process stream is sent into the sieve beds, the heat exchanger has to be shut down and restarted. It then takes 20-30 minutes to get the process running at full speed, resulting in decreased throughput and increased energy costs. This type of upset occurred every other week.

If the upset occurs and the sieve beds get wet, the process shutdown lasts between 36 and 48 hours because the beds must be shut down, regenerated, and restarted. While this type of upset is not common, wet sieve bed occurrences eventually lead to extensive equipment damage that combined cost over $200,000.

To address these challenges, Absolute Energy replaced the DP measurement with Emerson’s Rosemount 5301 Guided Wave Radar (GWR) and a Rosemount 9901 Chamber.

Emerson’s Rosemount 5301 Guided Wave Radars mounted on a Rosemount 9901 chamber for condensate receiver level control. Courtesy: Emerson Process ManagementThis Rosemount 5301 GWR provides a highly accurate and reliable direct level measurement. The major advantage of GWR technology is that it is independent of density changes and it manages changing pressure conditions without compromising reliability.

A Rosemount 9901 self-contained chamber was installed for externally mounting the Rosemount GWR to the vessel. This arrangement enables the instrument to be isolated for routine maintenance while keeping the plant operational. Installation was very easy, as the chamber was simply mounted on the existing process connections.

The improved control of levels in the condensate receiver means this measurement point is no longer a maintenance headache. As a result, Absolute Energy has increased plant availability, decreased energy and utilities costs, reduced maintenance costs, and lowered the risk of equipment damage.

Emerson Process Management

www.EmersonProcess.com

- Edited by Amanda McLeman, Control Engineering, www.controleng.com



No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
Each year, a panel of Control Engineering editors and industry expert judges select the System Integrator of the Year Award winners.
Control Engineering Leaders Under 40 identifies and gives recognition to young engineers who...
Learn more about methods used to ensure that the integration between the safety system and the process control...
Adding industrial toughness and reliability to Ethernet eGuide
Technological advances like multiple-in-multiple-out (MIMO) transmitting and receiving
Virtualization advice: 4 ways splitting servers can help manufacturing; Efficient motion controls; Fill the brain drain; Learn from the HART Plant of the Year
Two sides to process safety: Combining human and technical factors in your program; Preparing HMI graphics for migrations; Mechatronics and safety; Engineers' Choice Awards
Detecting security breaches: Forensic invenstigations depend on knowing your networks inside and out; Wireless workers; Opening robotic control; Product exclusive: Robust encoders
The Ask Control Engineering blog covers all aspects of automation, including motors, drives, sensors, motion control, machine control, and embedded systems.
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
News and comments from Control Engineering process industries editor, Peter Welander.
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
This is a blog from the trenches – written by engineers who are implementing and upgrading control systems every day across every industry.
Anthony Baker is a fictitious aggregation of experts from Callisto Integration, providing manufacturing consulting and systems integration.
Integrator Guide

Integrator Guide

Search the online Automation Integrator Guide
 

Create New Listing

Visit the System Integrators page to view past winners of Control Engineering's System Integrator of the Year Award and learn how to enter the competition. You will also find more information on system integrators and Control System Integrators Association.

Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Control Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.