Machine Safety: My main disconnect e-stop isn’t red with a yellow background

Does my main disconnect functioning as an e-stop need to be red with a yellow background?

07/05/2012


Jokab Safety giant E-Stop at Pack Expo 2010Does my main disconnect functioning as an e-stop need to be red with a yellow background?

 

This has long been an active area of discussion in manufacturing. In fact, using a main disconnect as an emergency device for removal of power has a long history. Some of us might remember when machines evolved to having their own machine mounted motor and or drive. Soon after this evolution the crow bar circuit emerged for emergency stopping a machine. I expect young folks today would laugh at seeing someone pick up a crow bar and throw it at the three main leads shorting out the current. An e-stop was born!

 

Banner Engineering's 30mm Mount Illuminated Emergency Stop Pushbutton is IP65-rated and is designed for emergency stop safety applications. Courtesy: Banner EngineeringFast forward to today and realize that the discussion about main disconnects being used as an e-stop device was only recently updated in NFPA 79 – 2007, Clause 10.7.4 Local Operation of the Supply Disconnecting Means to Effect Emergency Stop. The last updated NFPA 79 – 2012 made no changes to these requirements. The requirements of this Clause are: 

10.7.4.1 The supply disconnecting means shall be permitted to be locally operated to serve the function of emergency stop as follows:

Safety integration webcast, Control Engineering at www.controleng.com/webcast(1) Where it is readily accessible to the operator

(2) Where it is of the type described in 5.3.2(1), 5.3.2(2), or 5.3.2(3)

10.7.4.2 Where used as an emergency stop, the supply disconnecting means shall meet the color requirements of 10.7.3.

10.7.4.3 Disconnecting (isolating) electrical devices as described in 5.5.4, where accessible to the operator, shall also be permitted to serve the function of emergency stop. _____________________________________________________________ 

The additional requirements that I understand are that every machine needs to have at least one e-stopping device as determined by the risk assessment, that it needs to be red with a yellow background per 10.7.3 and that it needs to be accessible by the operator. ANSI B11.19 – Performance Criteria for Safeguarding normatively references NFPA 79 – 2007 as required.

Is anyone still confused?

 

Your comments or suggestion are always welcome so please let us know your thoughts. Submit your ideas, experiences, and challenges on this subject in the comments section below. Click here controleng.com/blogs if you don't see a comments box, find, and click into: Machine Safety: My main disconnect e-stop isn’t red with a yellow background, and scroll down.

 

Related reading and articles:

ANSI B11.19-2010, Performance Criteria for Safeguarding

NFPA 79 – 2012, Electrical Standard for Industrial Machinery

E-Stops and Your Compliance

E-Stops Aren’t Safety Devices

 

Contact: www.jbtitus.com for “Solutions for Machine Safety”.



No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
Each year, a panel of Control Engineering editors and industry expert judges select the System Integrator of the Year Award winners.
Control Engineering Leaders Under 40 identifies and gives recognition to young engineers who...
Learn more about methods used to ensure that the integration between the safety system and the process control...
Adding industrial toughness and reliability to Ethernet eGuide
Technological advances like multiple-in-multiple-out (MIMO) transmitting and receiving
Virtualization advice: 4 ways splitting servers can help manufacturing; Efficient motion controls; Fill the brain drain; Learn from the HART Plant of the Year
Two sides to process safety: Combining human and technical factors in your program; Preparing HMI graphics for migrations; Mechatronics and safety; Engineers' Choice Awards
Detecting security breaches: Forensic invenstigations depend on knowing your networks inside and out; Wireless workers; Opening robotic control; Product exclusive: Robust encoders
The Ask Control Engineering blog covers all aspects of automation, including motors, drives, sensors, motion control, machine control, and embedded systems.
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
News and comments from Control Engineering process industries editor, Peter Welander.
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
This is a blog from the trenches – written by engineers who are implementing and upgrading control systems every day across every industry.
Anthony Baker is a fictitious aggregation of experts from Callisto Integration, providing manufacturing consulting and systems integration.
Integrator Guide

Integrator Guide

Search the online Automation Integrator Guide
 

Create New Listing

Visit the System Integrators page to view past winners of Control Engineering's System Integrator of the Year Award and learn how to enter the competition. You will also find more information on system integrators and Control System Integrators Association.

Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Control Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.