Choosing analog communication protocols

Are all HART-enabled instruments 4-20 mA? Are there other options?

03/30/2012


Dear Control Engineering: After reading the article on using HART in an asset management program, I was wondering if all HART-enabled devices use a 4-20 mA analog signal, or if there are other options.

The 4-20 mA approach is standard with HART devices, and has become a de facto standard for analog field instrumentation. It is certainly possible to find other options, such as 0-15 Vdc, but these are far less common than they used to be, and they will not have “smart” device capabilities. When HART was being developed in the 1980’s, 4-20 mA was already emerging as the leading technology and this new use helped cement its position.

Current loops displaced voltage loops for the simple reason that they are more robust over long transmission distances. Voltage is more affected by wire resistance. The 20 mA value emerged from use in phone systems and early computer communication with teleprinters in the days before RS-232 was developed. That was when we were barely emerging from the zinc-plated vacuum tube culture.

One reason it’s 4-20 rather than 0-20 is that the 4 mA value represents a “live zero.” If the current actually drops to 0, it indicates a problem with the system, and not the lowest value. Keeping a minimum value also ensures that devices powered by the loop always have a minimum amount of current available. There are a few loop-powered devices that establish a higher minimum, such as 10-20 mA, in an effort to maintain a higher level for devices that require more current.

Peter Welander, pwelander(at)cfemedia.com



No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
Each year, a panel of Control Engineering editors and industry expert judges select the System Integrator of the Year Award winners.
Nominate today - Control Engineering Leaders Under 40 identifies and gives recognition to young engineers who...
Learn more about methods used to ensure that the integration between the safety system and the process control...
Adding industrial toughness and reliability to Ethernet eGuide
Technological advances like multiple-in-multiple-out (MIMO) transmitting and receiving
Robotic innovations, safety, Industrial energy management, Lambda tuning for PID, HMIs: All about software
CNC Way beyond traditional; Remote I/O, new approaches; Inside Process: APC, PID, cyber-security
Servodrive Control: Precise Power, PLCs vs. PACs, Virtualization, Best Products: Engineers' Choice Awards
The Ask Control Engineering blog covers all aspects of automation, including motors, drives, sensors, motion control, machine control...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
News and comments from Control Engineering process industries editor, Peter Welander.
Integrator Guide

Integrator Guide

Search the online Automation Integrator Guide
 

Create New Listing

Visit the System Integrators page to view past winners of Control Engineering's System Integrator of the Year Award and learn how to enter the competition. You will also find more information on system integrators and Control System Integrators Association.

Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Control Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.


Poll of the Week

How integrated are your maintenance, controls, and instrumentation systems?
Fully integrated
Somewhat integrated
Loosely integrated
They're not


Click Here for Poll Archives
Sponsored by:

CFEMedia.com | Subscribe to Magazine | Advertise | Contact Us | About Us | Site Map | Privacy Policy
Channels | New Products | Media Library | Connect | Industry News | Events and Awards | Newsletters | Blogs | Magazine
Control Engineering | Plant Engineering | Consulting-Specifying Engineer
All content copyright © 2010-2013 CFE Media. All rights reserved.