Choosing output formats for instrumentation transmitters

Why isn’t it easier to offer user selectability of signal format for field devices?

05/06/2011


Dear Control Engineering: The article about new gas flowmeters says that the company is using a more modular transmitter that makes it easier for the user to select a signal format. Why aren’t more companies doing that? Having to change field devices is a major drag on trying to use a more sophisticated networking technology.

 

One of the more interesting aspects of the flowmeters that FCI has introduced is the modularity of its transmitter. While most devices are hard wired to one specific format (e.g., 4-20 mA with HART or Foundation fieldbus), these new devices offer a plug-in module to allow users to change the output format.

I don’t know if this is the first time somebody has done this, but it certainly is not a common feature. Typically a transmitter is indeed fixed to a given protocol. This fact has made the process of migrating to a more sophisticated networking protocol much more expensive. For example, if all the devices in a process unit use 4-20 mA or some older analog voltage signal, you’ll probably have to replace them all if you want to move to a fieldbus. FCI has promised that its new transmitter is future proof in the sense that if you do need to make such a change, you can change the module (assuming the right format is available) and not the whole device. The company plans on using this approach with larger portions of its product line as time goes on.

To my thinking, a typical flowmeter or pressure sensor ought to come with a universal transmitter that is software configurable or you set a group of DIP switches to give the connectivity you want. Set it yourself for anything from 4-20 mA, Modbus, USB, Profibus, Foundation fieldbus, or any number of industrial Ethernet flavors. Maybe we’ll even throw in wireless. That isn’t quite practical yet, but I doubt it is far away. Some protocols still depend on a dedicated ASIC which is probably why having a plug-in component is still a requirement. My approach is probably still much too expensive, but might be here sooner than you think.

Subscribe to our Process Instrumentation & Sensors eNewsletter.

Peter Welander, pwelander@cfemedia.com



No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
The System Integrator Giants program lists the top 100 system integrators among companies listed in CFE Media's Global System Integrator Database.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
This eGuide illustrates solutions, applications and benefits of machine vision systems.
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Motor specification guidelines; Understanding multivariable control; Improving a safety instrumented system; 2017 Engineers' Choice Award Winners
Selecting the best controller from several viewpoints; System integrator advice for the IIoT; TSN and real-time Ethernet; Questions to ask when selecting a VFD; Action items for an aging PLC/DCS
Robot advances in connectivity, collaboration, and programming; Advanced process control; Industrial wireless developments; Multiplatform system integration
Motion control advances and solutions can help with machine control, automated control on assembly lines, integration of robotics and automation, and machine safety.
This article collection contains several articles on the Industrial Internet of Things (IIoT) and how it is transforming manufacturing.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

Future of oil and gas projects; Reservoir models; The importance of SCADA to oil and gas
Big Data and bigger solutions; Tablet technologies; SCADA developments
SCADA at the junction, Managing risk through maintenance, Moving at the speed of data
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Jose S. Vasquez, Jr.
Fire & Life Safety Engineer; Technip USA Inc.

(copy 5)

click me