Communications integral to self-diagnosing control systems

Troubleshooting geographically large electrical control systems with a multimeter in hand can be very time consuming and, unless viewed as an exercise perk, very tiring as well. This is where systems with self-diagnostic capabilities can be useful. As a designer of very large mobile structures, such as aircraft maintenance docking systems and retractable stadium roof transporters, Uni-Systems L...

12/01/2003


Troubleshooting geographically large electrical control systems with a multimeter in hand can be very time consuming and, unless viewed as an exercise perk, very tiring as well. This is where systems with self-diagnostic capabilities can be useful.

As a designer of very large mobile structures, such as aircraft maintenance docking systems and retractable stadium roof transporters, Uni-Systems LLC specializes in control systems with built-in diagnostics. The company employs PLCs and remote I/O systems, such as GE Fanuc's 90-30 and 90-70 PLCs and its Genius remote I/O blocks and Genius-enabled variable frequency drives (VFDs).

Communicating via Genius bus, these I/O modules transmit, not only their state and values, but also send any errors back to the PLC. These errors can be internal, such as burned out I/O points or firmware errors, or external circuit or component faults.

How can an input point know what faults a connected circuit may have? It should normally have a high or low potential, and it should not know if a connected, normally open limit switch is shorted or merely closed. Instead of functioning as a standard discrete input, and merely regarding a signal as high or low, these I/O modules look for four different signal levels. Below 25% the circuit is "open," between 25 and 50% the circuit is "off," between 50 and 75% it is "on," and if the circuit is above 75% it is shorted (see figure).

So, the I/O block can differentiate these values, but how does the circuit provide them? All dry contacts, such as limit switches, must be fitted with two resistors: one in series and one in parallel with the contact. With the contact open, the input will see both resistors in series. With the contact closed, it will see only the series resistor. With the wires shorted prior to the switch/resistors, it will see a short. And, with the wires cut, it will sense no circuit. Output points are different, of course, but they work on the same principles, and can detect open circuit and overload/short conditions.

For solid-state devices, such as proximity switches, the resistors can generally be omitted. This is possible because the normal function of a two-wire style prox relies on a trickle current to keep it powered, so the same states described above can be sensed in a proximity switch.

Since our retractable roof application makes extensive use of plug connections to facilitate fast replacement, there is always the chance of connections being left unplugged. However, the roof's diagnostic system will report this to the PLC.

In addition, a dragging brake will always cause problems. To prevent this from happening, each brake coil is tested through the above diagnostic, and then equipped with a switch that opens with the brake disk. This allows a startup to be safely aborted before the VFDs reach a significant frequency if a brake fails to open. This makes it vital for the system to be able to detect a switch failure.

For more information, visit www.uni-systems.com .

Input

External Impedance

Internal Impedance

Signal Voltage

Circuit Condition

27

25.9k Ohm

11.9k Ohm

37.7V

Normal, Open

28

3.9k Ohm

11.9k Ohm

90.4V

Normal, Closed

29

Infinite

11.9k Ohm

0V

Disconnected

30

0 Ohm

11.9k Ohm

120V

Shorted


Author Information

Lennart Nielsen is senior electrical engineer at Uni-Systems LLC , Minneapolis, MN.




No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
The System Integrator Giants program lists the top 100 system integrators among companies listed in CFE Media's Global System Integrator Database.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
This eGuide illustrates solutions, applications and benefits of machine vision systems.
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Sensor-to-cloud interoperability; PID and digital control efficiency; Alarm management system design; Automotive industry advances
Make Big Data and Industrial Internet of Things work for you, 2017 Engineers' Choice Finalists, Avoid control design pitfalls, Managing IIoT processes
Engineering Leaders Under 40; System integration improving packaging operation; Process sensing; PID velocity; Cybersecurity and functional safety
This article collection contains several articles on the Industrial Internet of Things (IIoT) and how it is transforming manufacturing.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

SCADA at the junction, Managing risk through maintenance, Moving at the speed of data
Flexible offshore fire protection; Big Data's impact on operations; Bridging the skills gap; Identifying security risks
The digital oilfield: Utilizing Big Data can yield big savings; Virtualization a real solution; Tracking SIS performance
click me