Comparing enclosure standards

As a way of standardizing enclosure performance, organizations like NEMA (National Electrical Manufacturers Association), UL (Underwriters Laboratories), CSA (Canadian Standards Association), IEC (International Electrotechnical Commission), VDE (Institute of German Electronics Engineers), and TÜV Rheinland of North America use rating systems to identify an enclosure's ability to resi...

03/01/1999


As a way of standardizing enclosure performance, organizations like NEMA (National Electrical Manufacturers Association), UL (Underwriters Laboratories), CSA (Canadian Standards Association), IEC (International Electrotechnical Commission), VDE (Institute of German Electronics Engineers), and TÜV Rheinland of North America use rating systems to identify an enclosure's ability to resist external environmental influences. Resistance to everything from dripping liquid, to hose-down, to total submersion is defined by the rating systems. These ratings are intended to provide more informed choices and ultimately a safer work area. However, there are differences among them.

In North America NEMA, UL, and CSA are the commonly recognized organizations. Their ratings are based on similar application descriptions and expected performance. UL and CSA both require enclosure testing by qualified evaluator labs. They also send site inspectors to ensure manufacturers adhere to prescribed methods and material specifications. NEMA does not require independent testing and leaves compliance up to the manufacturer.

North American enclosure rating systems also include a 4X rating that indicates resistance to corrosion. This rating is based on the enclosure's ability to withstand prolonged exposure to saltwater spray.

A 4X rating is a good indicator that an enclosure can resist corrosion; it does not provide information on how a specific corrosive agent will affect a given enclosure material. It is best to analyze the specific application and environment to determine the best enclosure choice.

European ratings

In Europe, IEC ratings are based on performance criteria similar to NEMA, with different interpretations of enclosure performance. For example, UL and CSA test requirements specify failure of the watertight test if a single drop of water enters the enclosure. IEC's standards for each ingress protection (IP) level specifies the amount of water allowed entering the enclosure.

IEC does not specify degrees of protection against risk of explosions or conditions such as moisture or corrosive vapors; NEMA does. Because of this reason and because tests and evaluations for other characteristics are not identical, IEC enclosure classification designations cannot be exactly equated with NEMA enclosure type numbers.

IEC uses IP ratings to define the degree of protection provided by an enclosure using a two-digit numerical classification. The first number defines the degree of protection against solid objects; and the second number defines the degree of protection against water.

To promote free trade movement to and from the European Union (EU), directives are being harmonized for health, safety, environment, and consumer protection using the CE (Conformite Europeenne) Mark.

For industrial control systems, the CE Mark appears only on enclosures containing all active control system components. Responsibility of ensuring compliance to applicable EU directives and harmonized standards belongs with the final equipment manufacturer.

This information was obtained from Hoffman (Anoka, Minn.) and Rittal (Springfield, O.). Most enclosure manufacturer catalogs and/or web sites explain enclosure related standards.

Enclosure Rating Descriptions

NEMA, UL, & CSA type rating

Approximate IEC/IP classification

Abbreviated protection description

Source: Control Engineering
Visit www.controleng.com/info : for a complete listing of NEMA, UL, CSA and IEC standards and ratings.

1

IP23

Indoor protection from contact with contents.

2

IP30

Indoor with limited protection from dirt & water.

3

IP64

Outdoor with some protection from rain, sleet, windblown dust, and ice damage.

3R

IP32

Outdoor with some protection from rain, sleet, and ice damage.

4

IP66

Indoor and outdoor with some protection from windblown dust, rain, splashing water, hose-directed water, and ice damage.

4X

IP66

Indoor and outdoor with some protection from cor rosion, windblown dust, rain, splashing water, hose-directed water, and ice damage.

6

IP67

Indoor and outdoor with protection from hose-directed water, entry of water during submersion at limited depth, ice damage.

12

IP55

Indoor with protection from dust, falling dirt, and drip ping non-corrosive liquids.

13

IP65

Indoor with protection against dust, spraying water, oil, and non-corrosive liquids.


Author Information

Dave Harrold, senior editor dharrold@cahners.com




No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
The System Integrator Giants program lists the top 100 system integrators among companies listed in CFE Media's Global System Integrator Database.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
This eGuide illustrates solutions, applications and benefits of machine vision systems.
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Motor specification guidelines; Understanding multivariable control; Improving a safety instrumented system; 2017 Engineers' Choice Award Winners
Selecting the best controller from several viewpoints; System integrator advice for the IIoT; TSN and real-time Ethernet; Questions to ask when selecting a VFD; Action items for an aging PLC/DCS
Robot advances in connectivity, collaboration, and programming; Advanced process control; Industrial wireless developments; Multiplatform system integration
Motion control advances and solutions can help with machine control, automated control on assembly lines, integration of robotics and automation, and machine safety.
This article collection contains several articles on the Industrial Internet of Things (IIoT) and how it is transforming manufacturing.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

Future of oil and gas projects; Reservoir models; The importance of SCADA to oil and gas
Big Data and bigger solutions; Tablet technologies; SCADA developments
SCADA at the junction, Managing risk through maintenance, Moving at the speed of data
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Jose S. Vasquez, Jr.
Fire & Life Safety Engineer; Technip USA Inc.
click me