Let’s discuss the copper

Data center owners are opting for even larger servers, adding even more copper.

06/20/2012


Last week, we discussed the differences in construction costs and copper requirements between the competing approaches of locating medium-voltage transformations outdoors, and connecting the secondary loads via large underground duct banks, versus moving the transformations indoors, in close proximity to the loads.

 

Image of multiple duct banks with 12 4'' conduits. Courtesy: Joe Guentert 

 

The differences between the two approaches are becoming more pronounced recently, as more and more data center owners are opting for 230 V servers, and are distributing large critical power at 415 Y/240 V. That necessitates a full-size (and sometimes, an OVERSIZED) neutral, which adds at least another third to the tonnage and the cost of the copper in secondary feeders. I have seen some very large data center designs on the boards recently that will have more than 4 million lbs of copper in underground duct banks or cable tray, just to get 600, 480, or 415 V utility power and generator power into the low-voltage main distribution switchgear lineups, before the power is even distributed to any loads.

 

Some large data center owners who are moving to modular containers in their centers also have moved to switchgear containers and skid-mounted unit substations outdoors, close-coupling the transformations to the secondary switchgear. That removes all the copper between the transformer and the switchgear, but then adds back even MORE copper on the distribution feeders from the switchgear into the loads.

           

I’ve seen “modular” projects recently where the secondary switchgear was located outdoors, close-coupled to substation transformers, eliminating the need for a 4000 A or so secondary duct banks into the building. But those 4000 A trunk feeders were then replaced by branch distribution feeders in duct banks or cable tray having a total aggregate ampacity of 10,000 A or more, to distribute to the loads.

 

Image of multiple duct banks with 16 4'' conduits. Courtesy: Joe Guentert

 

I think that this pronounced trend of load growth cries out more loudly than ever before in history for a real and true “loadcenter” approach, with the transformations located right down in the center of the loads, where little 4000 A braided flex links like these, connecting a transformer to its secondary switchgear, can replace all those duct banks and hundred of tons of copper.

 

Image of 4000 A braided flex links, connecting a transformer to its secondary switchgear. Courtesy: Joe Guentert

 

If you can accept that this makes sense, what are the options? Until fairly recently, almost all of the loadcenter substation transformers that went inside data centers since 1995 were either VPI dry-type or epoxy cast coil construction.



No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
Each year, a panel of Control Engineering editors and industry expert judges select the System Integrator of the Year Award winners.
Control Engineering Leaders Under 40 identifies and gives recognition to young engineers who...
Learn more about methods used to ensure that the integration between the safety system and the process control...
Adding industrial toughness and reliability to Ethernet eGuide
Technological advances like multiple-in-multiple-out (MIMO) transmitting and receiving
Virtualization advice: 4 ways splitting servers can help manufacturing; Efficient motion controls; Fill the brain drain; Learn from the HART Plant of the Year
Two sides to process safety: Combining human and technical factors in your program; Preparing HMI graphics for migrations; Mechatronics and safety; Engineers' Choice Awards
Detecting security breaches: Forensic invenstigations depend on knowing your networks inside and out; Wireless workers; Opening robotic control; Product exclusive: Robust encoders
The Ask Control Engineering blog covers all aspects of automation, including motors, drives, sensors, motion control, machine control, and embedded systems.
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
News and comments from Control Engineering process industries editor, Peter Welander.
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
This is a blog from the trenches – written by engineers who are implementing and upgrading control systems every day across every industry.
Anthony Baker is a fictitious aggregation of experts from Callisto Integration, providing manufacturing consulting and systems integration.
Integrator Guide

Integrator Guide

Search the online Automation Integrator Guide
 

Create New Listing

Visit the System Integrators page to view past winners of Control Engineering's System Integrator of the Year Award and learn how to enter the competition. You will also find more information on system integrators and Control System Integrators Association.

Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Control Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.