Machine Safety: My main disconnect e-stop isn’t red with a yellow background

Does my main disconnect functioning as an e-stop need to be red with a yellow background?

07/05/2012


Jokab Safety giant E-Stop at Pack Expo 2010Does my main disconnect functioning as an e-stop need to be red with a yellow background?

 

This has long been an active area of discussion in manufacturing. In fact, using a main disconnect as an emergency device for removal of power has a long history. Some of us might remember when machines evolved to having their own machine mounted motor and or drive. Soon after this evolution the crow bar circuit emerged for emergency stopping a machine. I expect young folks today would laugh at seeing someone pick up a crow bar and throw it at the three main leads shorting out the current. An e-stop was born!

 

Banner Engineering's 30mm Mount Illuminated Emergency Stop Pushbutton is IP65-rated and is designed for emergency stop safety applications. Courtesy: Banner EngineeringFast forward to today and realize that the discussion about main disconnects being used as an e-stop device was only recently updated in NFPA 79 – 2007, Clause 10.7.4 Local Operation of the Supply Disconnecting Means to Effect Emergency Stop. The last updated NFPA 79 – 2012 made no changes to these requirements. The requirements of this Clause are: 

10.7.4.1 The supply disconnecting means shall be permitted to be locally operated to serve the function of emergency stop as follows:

Safety integration webcast, Control Engineering at www.controleng.com/webcast(1) Where it is readily accessible to the operator

(2) Where it is of the type described in 5.3.2(1), 5.3.2(2), or 5.3.2(3)

10.7.4.2 Where used as an emergency stop, the supply disconnecting means shall meet the color requirements of 10.7.3.

10.7.4.3 Disconnecting (isolating) electrical devices as described in 5.5.4, where accessible to the operator, shall also be permitted to serve the function of emergency stop. _____________________________________________________________ 

The additional requirements that I understand are that every machine needs to have at least one e-stopping device as determined by the risk assessment, that it needs to be red with a yellow background per 10.7.3 and that it needs to be accessible by the operator. ANSI B11.19 – Performance Criteria for Safeguarding normatively references NFPA 79 – 2007 as required.

Is anyone still confused?

 

Your comments or suggestion are always welcome so please let us know your thoughts. Submit your ideas, experiences, and challenges on this subject in the comments section below. Click here controleng.com/blogs if you don't see a comments box, find, and click into: Machine Safety: My main disconnect e-stop isn’t red with a yellow background, and scroll down.

 

Related reading and articles:

ANSI B11.19-2010, Performance Criteria for Safeguarding

NFPA 79 – 2012, Electrical Standard for Industrial Machinery

E-Stops and Your Compliance

E-Stops Aren’t Safety Devices

 

Contact: www.jbtitus.com for “Solutions for Machine Safety”.



No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
Each year, a panel of Control Engineering editors and industry expert judges select the System Integrator of the Year Award winners.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Learn how to create value with re-use; gain productivity with lean automation and connectivity, and optimize panel design and construction.
Go deep: Automation tackles offshore oil challenges; Ethernet advice; Wireless robotics; Product exclusives; Digital edition exclusives
Lost in the gray scale? How to get effective HMIs; Best practices: Integrate old and new wireless systems; Smart software, networks; Service provider certifications
Fixing PID: Part 2: Tweaking controller strategy; Machine safety networks; Salary survey and career advice; Smart I/O architecture; Product exclusives
The Ask Control Engineering blog covers all aspects of automation, including motors, drives, sensors, motion control, machine control, and embedded systems.
Look at the basics of industrial wireless technologies, wireless concepts, wireless standards, and wireless best practices with Daniel E. Capano of Diversified Technical Services Inc.
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
This is a blog from the trenches – written by engineers who are implementing and upgrading control systems every day across every industry.
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Control Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.