Machine Safety: My main disconnect e-stop isn’t red with a yellow background

Does my main disconnect functioning as an e-stop need to be red with a yellow background?


Jokab Safety giant E-Stop at Pack Expo 2010Does my main disconnect functioning as an e-stop need to be red with a yellow background?


This has long been an active area of discussion in manufacturing. In fact, using a main disconnect as an emergency device for removal of power has a long history. Some of us might remember when machines evolved to having their own machine mounted motor and or drive. Soon after this evolution the crow bar circuit emerged for emergency stopping a machine. I expect young folks today would laugh at seeing someone pick up a crow bar and throw it at the three main leads shorting out the current. An e-stop was born!


Banner Engineering's 30mm Mount Illuminated Emergency Stop Pushbutton is IP65-rated and is designed for emergency stop safety applications. Courtesy: Banner EngineeringFast forward to today and realize that the discussion about main disconnects being used as an e-stop device was only recently updated in NFPA 79 – 2007, Clause 10.7.4 Local Operation of the Supply Disconnecting Means to Effect Emergency Stop. The last updated NFPA 79 – 2012 made no changes to these requirements. The requirements of this Clause are: The supply disconnecting means shall be permitted to be locally operated to serve the function of emergency stop as follows:

Safety integration webcast, Control Engineering at Where it is readily accessible to the operator

(2) Where it is of the type described in 5.3.2(1), 5.3.2(2), or 5.3.2(3) Where used as an emergency stop, the supply disconnecting means shall meet the color requirements of 10.7.3. Disconnecting (isolating) electrical devices as described in 5.5.4, where accessible to the operator, shall also be permitted to serve the function of emergency stop. _____________________________________________________________ 

The additional requirements that I understand are that every machine needs to have at least one e-stopping device as determined by the risk assessment, that it needs to be red with a yellow background per 10.7.3 and that it needs to be accessible by the operator. ANSI B11.19 – Performance Criteria for Safeguarding normatively references NFPA 79 – 2007 as required.

Is anyone still confused?


Your comments or suggestion are always welcome so please let us know your thoughts. Submit your ideas, experiences, and challenges on this subject in the comments section below. Click here if you don't see a comments box, find, and click into: Machine Safety: My main disconnect e-stop isn’t red with a yellow background, and scroll down.


Related reading and articles:

ANSI B11.19-2010, Performance Criteria for Safeguarding

NFPA 79 – 2012, Electrical Standard for Industrial Machinery

E-Stops and Your Compliance

E-Stops Aren’t Safety Devices


Contact: for “Solutions for Machine Safety”.

No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
The System Integrator Giants program lists the top 100 system integrators among companies listed in CFE Media's Global System Integrator Database.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
This eGuide illustrates solutions, applications and benefits of machine vision systems.
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Choosing controllers: PLCs, PACs, IPCs, DCS? What's best for your application?; Wireless trends; Design, integration; Manufacturing Day; Product Exclusive
Variable speed drives: Smooth, efficient, electrically quite motion control; Process control upgrades; Mobile intelligence; Product finalists: Vote now; Product Exclusives
Machine design tips: Pneumatic or electric; Software upgrades; Ethernet advantages; Additive manufacturing; Engineering Leaders; Product exclusives: PLC, HMI, IO
This article collection contains the 5 most referenced articles on improving the use of PID.
Learn how Industry 4.0 adds supply chain efficiency, optimizes pricing, improves quality, and more.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

Cyber security cost-efficient for industrial control systems; Extracting full value from operational data; Managing cyber security risks
Drilling for Big Data: Managing the flow of information; Big data drilldown series: Challenge and opportunity; OT to IT: Creating a circle of improvement; Industry loses best workers, again
Pipeline vulnerabilities? Securing hydrocarbon transit; Predictive analytics hit the mainstream; Dirty pipelines decrease flow, production—pig your line; Ensuring pipeline physical and cyber security