Medium-voltage breaker switchgear example (oil-filled power transformer)

Below is an example of a MV breaker switchgear feeding a 12 MVA power transformer.

09/25/2013


Figure 2: Single line and time-current curves illustrate a typical transformer protection scheme for transformer greater than 3 MVA using MV breakers and relay protection. Courtesy: JBA Consulting EngineersFigure 2 illustrates a medium-voltage (MV) breaker switchgear feeding a 12 MVA oil-filled power transformer. It includes the primary and secondary protection of the transformer circuit along with its associated feeder cables. The transformer circuit consists of:

  • Originating source: Customer-owned 22 kV metal enclosed switchgear vacuum breaker
  • Secondary circuit breaker: 4.16 kV vacuum breaker within enclosed breaker switchgear
  • Primary protection: Device 50 and 51 3-phase, 50/51GP ground fault protection
  • Secondary protection: Device 50 and 51 3-phase, 50/51GP ground fault protection
  • Primary cable: Two #500KCM underground 25 kV EPR MV 105 cables in conduit
  • Secondary cables: Two #500 KCMIL underground 5/8KV EPR 133% insulation cables in conduit
  • Transformer rating: 12/13.4 MVA, 12.47 kV D to 4.16 kV U, Z=9%

The following protective features are illustrated:

  • Primary overcurrent curve is to the right of the transformer’s 12 times FLA inrush point and to the left of the cable damage curve.
  • For primary and secondary protection with a transformer impedance of 10% or less, the NEC requires that the primary breaker not be larger than 400% of primary FLA and the secondary 4.16 kV breaker must not be larger than 250% of secondary FLA.
    • Primary: The relay overcurrent is set at 800 amps, which is 125% continuous of the 13.2 MVA/636 FLA of the transformer—within NEC guidelines
    • Secondary: The relay overcurrent is set at 2000 amps, which is 110% continuous of the 13.2 MVA/1834 FLA of the transformer—within NEC guidelines
  • Both the primary and secondary cable damage curves are above the maximum fault current at 0.01 s.
  • The minimum clear time between the breakers is 0.312 s, which is greater than the minimum 0.2 s guidelines.
  • Primary and secondary ground fault protection is selectively coordinated. 

Leslie Fernandez is senior project engineer, electrical at JBA Consulting Engineers. He has more than 28 years of engineering and design and field experience that includes MV distribution systems for military, mining, tunneling, food manufacturing, power production facilities, high-rise facilities, and casino resort complexes. 



No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
Each year, a panel of Control Engineering editors and industry expert judges select the System Integrator of the Year Award winners.
Control Engineering Leaders Under 40 identifies and gives recognition to young engineers who...
Learn more about methods used to ensure that the integration between the safety system and the process control...
Adding industrial toughness and reliability to Ethernet eGuide
Technological advances like multiple-in-multiple-out (MIMO) transmitting and receiving
Virtualization advice: 4 ways splitting servers can help manufacturing; Efficient motion controls; Fill the brain drain; Learn from the HART Plant of the Year
Two sides to process safety: Combining human and technical factors in your program; Preparing HMI graphics for migrations; Mechatronics and safety; Engineers' Choice Awards
Detecting security breaches: Forensic invenstigations depend on knowing your networks inside and out; Wireless workers; Opening robotic control; Product exclusive: Robust encoders
The Ask Control Engineering blog covers all aspects of automation, including motors, drives, sensors, motion control, machine control, and embedded systems.
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
News and comments from Control Engineering process industries editor, Peter Welander.
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
This is a blog from the trenches – written by engineers who are implementing and upgrading control systems every day across every industry.
Anthony Baker is a fictitious aggregation of experts from Callisto Integration, providing manufacturing consulting and systems integration.
Integrator Guide

Integrator Guide

Search the online Automation Integrator Guide
 

Create New Listing

Visit the System Integrators page to view past winners of Control Engineering's System Integrator of the Year Award and learn how to enter the competition. You will also find more information on system integrators and Control System Integrators Association.

Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Control Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.