Working together with Empire Control and Automation, Ross Point Water put together a control system that is both reliable and practical, using the latest technology. They decided to implement PLC/radio communication system that makes the district less dependant on the phone company for its daily operation.

03/30/2004


New Control System Delivers Clean Water to Growing Idaho Community

By Dean Huggins, JC Dean Diversified

Post Falls, Idaho is a small town that has been growing up. This small community of 19,000
people, located near the Idaho/Washington border, has experienced incredible population growth
in the last 10 years or so.

Along with this growth has come the need for water - lots of it. Ross Point Water District has the
responsibility of providing water for the ever-increasing demand. A prior control system at Ross
Point Water consisted of four wells and one reservoir tied together with long distance solid-state
relays from BW Controls. The relays were used to transmit signals via telephone wire for on/off
states, such as sensing the level of the reservoirs and turning pumps on and off. The lines
belonged to the phone company, who had to be contacted for repairs if something went wrong. If
the lease lines were at fault, the telephone company was not usually able to show up at a job site
on short notice and the repair time could be lengthy. For instance, if the probe leads from the
reservoir were damaged and disabled the BW relays, the level would have to be maintained
manually. This made for long nights for district water employees.

Working together with Empire Control and Automation, Ross Point Water put together a control
system that is both reliable and practical, using the latest technology. They decided to implement
a PLC/radio communication system that makes the district less dependant on the phone
company for its daily operation.

The new water system is made up of five AutomationDirect PLCs (DL05 and DL06 models), five
radios, an autodialer, and two AutomationDirect EZTouch touch screens and three EZText text
panels. “ AutomationDirect offered the best of all worlds - quality, dependability, and
affordability", says Dan Seldon of Ross Point Water.

The system monitors and controls water level, pressures, room temperature, well pump
operation, auto-manual settings and power water valve operations to provide clean water to
customers. The Primrose well, which is also the main office location, has a 75 HP vertical shaft
turbine pump and a DL06 PLC coupled to it, along with an EZTouch touch panel. Another well at
the 20 th St. location, about a mile north of Primrose, has a 125 HP vertical pump, a DL06, and an
EZTouch panel. To the West of 20 th St. is the Syringa well site, which includes a 100 HP well
pump with a DL05 PLC and an EZText text panel. The final well, Horsehaven, has a new 250 HP
pump, paired with a DL05 PLC and an EZText panel.

When the system is in automatic mode, all pumps are started and stopped by PLC outputs
connected to a relay timing system, which integrates with a valve attached to the pump discharge
line. The valve allows air, which fills the well casing when the pump is not running, to exit the
piping system at startup. This system prevents “water hammer”, a condition that can break large
pipes and cause much damage to homes.

The PLCs monitor the operation of the valve, shut down the system in case of failures, and notify
operators of alarms through the autodialer system. Each site has several alarm sensing inputs.
Each PLC is programmed to shut down its associated pump motor depending on the type of
alarm activated. An alarm can be acknowledged from any touch or text panel location at any of
the sites.

Northern Idaho outdoor temperatures can get down to -20 degrees in the winter and over 100
degrees in the summer. Freezing pipes are a concern in cold weather and overheating electric
motors are a concern in the summer, so all well house buildings are monitored for ambient
temperature. The PLC monitors the room temperature and sends an alarm to the autodialer if the
pre-set limits are reached. The PLC also monitors control voltage in the event of a power failure.
If control power is lost, a backup UPS installed at each location ensures that an alarm gets sent to the autodialer. Each UPS has a special circuit added, which sends signals to the PLC in the
event of UPS failure.

The electric motors at each well have been converted from “across the line” starters to soft
starters. The soft starters have auxiliary contacts that close if any one of five failures is detected
by the starter. These include loss of phase, shorted SCRs, over current, over speed, over voltage
and under voltage. The PLCs will send an alarm signal to the autodialer in the event of a soft
starter fault. Any significant drop in pressure in the system while the pump is running will activate
a timer in the PLC and will shut down the pump if pressure remains low.

The five sites are linked by radio transmission and each radio is connected to the PLC’s serial
port. Constant communication between all sites enabled the use of extensive failure alarms,
which is a valuable feature. Even if a pump is not being used, its radio system is still being
monitored for functionality. These alarm and shut down features are vital to the continued
operation of the water system and also protect expensive equipment from damage, thus saving
the water district money compared to prior repair expenses.

The radio system has helped save money on phone lines too. With the old system, when a “no
water” alarm was necessary, all sites except the 20 th St. location had a Motorola bag phone (cell
phone) connected as a dialer for the alarm. 20 th St. is now the only site that has a cell connection
for dialing out, eliminating several phones at the other sites. A new autodialer was also added at
the 20 th St. site, with 40 input capability. These inputs are integrated with the outputs of the DL06
at the 20 th St. well site. All alarm conditions that are monitored by AutomationDirect PLCs are
sent via radio transmission to 20 th St. The PLC at 20 th St. then activates the appropriate
autodialer input, which has been voice recorded to dial out to emergency personnel. The voice
recording tells the person on the phone what kind of alarm has been activated, such as “soft start
fault failure at Syringa” so employees may respond accordingly.

At the reservoir, a pressure transducer has been installed and the pressure is converted into feet
of water by the PLC. This information is then displayed on the three touch screens. The previous
system had sensor probes that dipped into the reservoir tank and connected to the leased lines,
eventually making relay contact back to Primrose. With this type of system, it was not possible to
know the reservoir levels or control them. The DL05 and DL06 PLCs with 4-20ma analog option
cards proved to be an excellent alternative to the probes. Now the reservoir level can be
monitored at a touch screen display and the set point levels can be adjusted from the office.
Reservoir high level and low level setpoints can also be adjusted from the touch panels.

Three reservoir booster pumps, one 5 HP and two 10 HP, supply water to specific areas because
the terrain in those areas make it impractical to supply water by gravity feed from the reservoir. A
fire pump is also installed at the site to supply large amounts of water to hydrants if needed. The
water system must be online and monitored at all times, especially when one considers life and
property may be at stake. Each booster pump can be placed in manual or auto mode. The water
supply line from the booster pumps also has a pressure transducer connected to the analog card
on the DL06. When pressure drops, booster pumps turn on to meet the demand.

Since water demand goes up dramatically in the summer, more pumps need to be online during
that time. In the past, it was necessary to travel to the sites to place a well into auto or manual
mode. With the new system, this is now accomplished with the touch of a button on the touch
panel at the Primrose location.

All in all, the system has been very successful. “We are now saving $350 per month on cell
phone and lease line bills and have seen an increase in uptime due to continued operation
without breakdown”, says Seldon. That kind of savings and increased efficiency not only makes
the system a success for the Water District, but also for their customers, who benefit from
outstanding service.





No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
The System Integrator Giants program lists the top 100 system integrators among companies listed in CFE Media's Global System Integrator Database.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
This eGuide illustrates solutions, applications and benefits of machine vision systems.
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Sensor-to-cloud interoperability; PID and digital control efficiency; Alarm management system design; Automotive industry advances
Make Big Data and Industrial Internet of Things work for you, 2017 Engineers' Choice Finalists, Avoid control design pitfalls, Managing IIoT processes
Engineering Leaders Under 40; System integration improving packaging operation; Process sensing; PID velocity; Cybersecurity and functional safety
This article collection contains several articles on the Industrial Internet of Things (IIoT) and how it is transforming manufacturing.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

SCADA at the junction, Managing risk through maintenance, Moving at the speed of data
Flexible offshore fire protection; Big Data's impact on operations; Bridging the skills gap; Identifying security risks
The digital oilfield: Utilizing Big Data can yield big savings; Virtualization a real solution; Tracking SIS performance
click me