Operating NEMA Premium motors above rated load cuts efficiency

The operating load of any motor depends on a number of factors and it can have a major impact on its efficiency

02/12/2014


The operating load of any motor depends on a number of factors. As the chart shows, it also affects motor efficiency. Data courtesy: Baldor Electric Co.Recently some motor manufacturers have begun to mark their motors with service factors (SFs) of 1.25 rather than the usual 1.15 number used for years. Although this may indicate one is receiving a more robust motor, the actual torque capability of the motor is not enhanced.

Operating at SF, the motor is also well past its peak efficiency and power factor (PF) peak and will use more energy for the work produced, and may experience reduced winding, bearing, and grease life.

Most motors used in North America are marked with a SF, which is defined by the National Electrical Manufacturers Association in MG 1-2011 as follows:

1.42 SF—ac motors: The SF of an AC motor is a multiplier which, when applied to the rated horsepower, indicates a permissible horsepower loading which may be carried under the conditions specified for the service factor (see Section 14.37: Application of alternating-current motors with service factors).

Section 14.37—Application of alternating-current motors with SFs:

When a motor is operated at any SF greater than 1, it may have efficiency, power factor, and speed different from those at rated load, but the locked-rotor torque and current and breakdown torque will remain unchanged.

A motor operating continuously at any SF greater than 1 will have a reduced life expectancy compared to operating at its rated nameplate horsepower. Insulation life and bearing life are reduced by the SF load.

Reduced winding, bearing, and grease life

Operation of a motor continuously above rated load raises the temperature rise of the motor. As a rule of thumb, for every 10 C hotter the motor operates, its insulation life is cut in half. If we look at a 100 hp NEMA Premium efficient TEFC motor, it has a temp rise of 60 C at rated load and 76 C at 1.15 SF, a 16 C difference. This means that the insulation life is cut by 250% over the motor operated at rated load.

The higher temperature operation also takes its toll on bearing and grease life. At rated load, the 100 hp motor would have a grease life of 5000 hours. When it is operated at 1.25 SF, the grease life is shortened to 1750 hours-a 285% reduction in grease life.

Operation above rated load reduces efficiency

The 100 hp motor discussed above has a nominal efficiency of 95.4% and a power factor of 82.6%. Operating this motor at a 1.25 SF reduces efficiency to 94.9% and PF to 87.4%. At rated load and operating continuously at $0.075/kWh, this same 100 hp motor uses $51,375 in electricity annually (685,000 kWh). When it is operated at a 1.25 SF and loaded to 125 hp, it uses $64,558 annually (852,680 kWh), an increase of $13,183.

Ideally the maximum efficiency for an ac induction motor is at about 80% of its rating, not above full load. Some process industries have adopted the 80% point as a best practice. A 150 hp motor operated at 80% load uses $61,138 and 815,173 kWh.

Some compressor companies also size motors to operate at SF, calling a motor that operates at rated load "oversized." Users should request a right-sized motor for best efficiency. The additional purchase cost of the larger motor will be easily offset by the lifecycle costs of a smaller motor operating in its SF. The purchase price of a motor is only about 2% of its lifecycle cost.

John Malinowski is general product manager and Jack Zedek is senior design engineer for Baldor Electric Company.



MICHAEL , Non-US/Not Applicable, Australia, 02/20/14 08:06 AM:

Excellent article on motor services factors. Need to work below SF rating to maximise service life and avoid down time
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
Each year, a panel of Control Engineering editors and industry expert judges select the System Integrator of the Year Award winners.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Learn how to create value with re-use; gain productivity with lean automation and connectivity, and optimize panel design and construction.
Go deep: Automation tackles offshore oil challenges; Ethernet advice; Wireless robotics; Product exclusives; Digital edition exclusives
Lost in the gray scale? How to get effective HMIs; Best practices: Integrate old and new wireless systems; Smart software, networks; Service provider certifications
Fixing PID: Part 2: Tweaking controller strategy; Machine safety networks; Salary survey and career advice; Smart I/O architecture; Product exclusives
The Ask Control Engineering blog covers all aspects of automation, including motors, drives, sensors, motion control, machine control, and embedded systems.
Look at the basics of industrial wireless technologies, wireless concepts, wireless standards, and wireless best practices with Daniel E. Capano of Diversified Technical Services Inc.
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
This is a blog from the trenches – written by engineers who are implementing and upgrading control systems every day across every industry.
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Control Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.