Safety Relays vs CAT 4; Comments on Safety, Redundancy, Risk

07/20/2009


July 20, 2009

Recently I visited a manufacturing company to discuss their machine guarding strategy for the control system on automated palletizer machines. After some discussion, I asked for a plant floor tour to see these machines being manufactured. During the tour they showed me a CAT 4 application mitigated by applying a CAT 4 rated safety relay. The owner also pointed out that they were able to generate a diagnostic fault on this circuit easily via the safety rated relay. Being immediately curious, I asked if they could describe how they accomplished the CAT 4 circuit including the fault display.

They answered by saying that the CAT 4 rated safety relay has two redundant latched circuits. So, we wired one output to the actuator and the second output to the operator display panel. Bingo, we have a CAT 4 circuit with diagnostics!

What’s wrong with this picture?

Posted by J.B. Titus on July 20, 2009

COMMENTS

September 2, 2009

In response to: Safety Relays vs CAT 4Federico Badillo commented:

 

To achive Cat 4, redundancy has to be applied to the outputs, double contactor (a model with linked contacts ) to stop the dangerous movement and monitoring of the contactors operation by the safety relay, about the inputs, using redundancy and oposite polarity at each channel to detect wiring faults.

September 2, 2009

In response to: Safety Relays vs CAT 4JSmith commented:

 

That is correct. The redundancy built into the device is what allows the device to be rated as CAT IV. What is truly interesting is when these devices are used in conjunction with a bus system such as profibus. I have built configurations with regular and safety IO sharing the same bus and still maintaining the CAT IV safety rating.

September 2, 2009

In response to: Safety Relays vs CAT 4BKelly commented:

 

The redundant channels are to ensure that the safety function is achieved on the failure of a single channel. This redundancy must be carried out to the actuators. i.e. if the goal is to shut down a motor then each channel must feed separate contactors and de-energizing either contactor removes power from the motor. The diagnostics should then be handled via auxiliary contacts on the actuators in conjunction with the (usually) normal closed monitoring contacts on the safety relay itself. In the configuration you describe a single failure in the channel connected to the actuator completely defeats the safety function and therefore would not meet category 4 requirements, regardless of the rating on the relay.



No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
The System Integrator Giants program lists the top 100 system integrators among companies listed in CFE Media's Global System Integrator Database.
Each year, a panel of Control Engineering and Plant Engineering editors and industry expert judges select the System Integrator of the Year Award winners in three categories.
This eGuide illustrates solutions, applications and benefits of machine vision systems.
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Additive manufacturing benefits; HMI and sensor tips; System integrator advice; Innovations from the industry
Robotic safety, collaboration, standards; DCS migration tips; IT/OT convergence; 2017 Control Engineering Salary and Career Survey
Integrated mobility; Artificial intelligence; Predictive motion control; Sensors and control system inputs; Asset Management; Cybersecurity
Featured articles highlight technologies that enable the Industrial Internet of Things, IIoT-related products and strategies to get data more easily to the user.
This article collection contains several articles on how automation and controls are helping human-machine interface (HMI) hardware and software advance.
This digital report will explore several aspects of how IIoT will transform manufacturing in the coming years.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

Infrastructure for natural gas expansion; Artificial lift methods; Disruptive technology and fugitive gas emissions
Mobility as the means to offshore innovation; Preventing another Deepwater Horizon; ROVs as subsea robots; SCADA and the radio spectrum
Future of oil and gas projects; Reservoir models; The importance of SCADA to oil and gas
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Jose S. Vasquez, Jr.
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me