Understanding Pressure Instrumentation

Measuring pressure is one of the most basic instrumentation functions in any industry. From an oil refinery to a bulldozer, measuring the pressure of compressed air, hydraulic fluid, process liquids, steam, or countless other media is a daily occurrence and critical to all manner of control. As a result, pressure measurement devices are everywhere, and there are countless varieties of options.

12/01/2006


AT A GLANCE

 

  • Concepts of pressure

  • Understand range and accuracy

  • Selecting pressure instruments

  • Smart transmitter capabilities

Sidebars:
Instrumentation nomenclature

Measuring pressure is one of the most basic instrumentation functions in any industry. From an oil refinery to a bulldozer, measuring the pressure of compressed air, hydraulic fluid, process liquids, steam, or countless other media is a daily occurrence and critical to all manner of control. As a result, pressure measurement devices are everywhere, and there are countless varieties of options. Reviewing technologies in general terms can yield better applications, although there likely will be exceptions to any specific point.

Pressure, also called compressive stress in mechanical terms, has peculiar characteristics that affect approaches to measure it:

  • It is usually quantified in units of force per unit of area; and,

  • It exists in both static and moving fluids;

  • Fluid pressure is always measured as a differential to something else.

Two types of pressure measurements can be divided into three categories:

  • Absolute pressure is measured against an absolute vacuum, discounting entirely the effects of atmospheric pressure. This measure is used primarily for research or design, but there are some applications where an absolute reading is useful in a process context. Since it isn’t practical to pull a full vacuum inside a sensor housing, sensors typically adjust a gage reading using either a fixed correction factor or more sophisticated units use a measured barometric pressure.

  • Differential pressure is the pressure in one area or vessel measured against another. The reading is the difference between the two and does not account for the pressure of either side relative to atmosphere or a vacuum.

  • Gage pressure, which is a type of differential pressure, is the pressure in one area or vessel measured against atmosphere. This is the most common practice.

The two most common units of pressure measurement are psi and bar. While the former is primarily still used in the U.S., the latter metric unit is becoming more common. Bar has largely replaced pascals and kilopascals since the numbers are more convenient. Many other units of measure exist, but their uses generally are relegated to specialized applications. Both psi and bar use a suffix “a” or “g” to indicate absolute or gage. When there is no suffix, gage is assumed.

Instrumentation

Traditional mechanical gages use a curved, closed 'bourdon tube' that tends to straighten as internal pressure increases.

Differential pressure measurements do not specify absolute or gage, since both sides of the measurement are compared directly. The reading is the difference and has no indication of the magnitude of the two sides. If the differential pressure between two tanks is 50 psi, the tanks could be 10 psi and 60 psi, or 5,000 psi and 5,050 psi. There is no way to determine pressure relative to atmosphere without another sensor. Differential pressures often use a suffix “d.”

Traditionally, mechanical gages with curved bourdon tubes were standard, and these are still available in many configurations. As with other forms of instrumentation, however, electronic versions have gained popularity.

Accuracy, range and safety

Electronic pressure instruments and mechanical gages express accuracy in the same way, specifying an error factor as a percentage of range. For example, a good quality 0-500 psi gage could offer accuracy ofoperating level while allowing for potential pressure surges or spikes. In other words, if your process runs at 75 psi, it is better to use a 0-100 psi gage rather than a 0-500 psi gage, even if they have the same accuracy rating. Poor ranging is frequently cited as the most common mistake when selecting and applying pressure devices. Cost-minded purchasers choose one pressure instrument for the sake of minimizing inventory and then try to make it work in a wide range of applications. Accuracy suffers as a result.

Sensors

This compressed air tank has both absolute and gage transducers. When charged to 100 psig, the absolute side reads 114.7 psia. If that tank were taken into outer space, both transducers would show the same reading since both are reading relative to an absolute vacuum.

Some transmitters can have their range adjusted electronically. For example, a unit designed to measure 0-500 psi can be electronically adjusted to read 0-300. This helps spread out the relevant reading area on the 4-20 mA signal, but does not actually increase accuracy. The turn-down ratio will be the same as the full 0-500 scale in most cases.

“There are $2 or $3 sensors that can go in your automobile tires and feed back to a panel on your dashboard. You don’t need a lot of accuracy or fast response to say that your right front tire is low,” says Tom Reid, product manager, GE-Druck. “The same thing could apply if you just want a ballpark reading of the pressure inside a tank. As long as the mechanism and housing will hold up, that may be all that matters. It all depends on how critical the process is.”

Victor Miller, pressure specialist with Wika Instrument, stresses how understanding an application determines the importance of range and ruggedness. “Users don’t take into account the dynamics of what is going on inside the system,” he observes. “When a fluid is moving and a valve opens or closes suddenly, it sends a pressure spike traveling at the speed of sound through the system that can tear apart a sensor, or at least knock it out of calibration.” Static applications and compressible fluids do not need as much protection from spikes as a more dynamic environment.

Selecting a pressure instrument

Once you have determined the measurement requirements for a specific application, you can choose an appropriate device based on other performance attributes beyond range and accuracy. Such considerations include:

Material : Instruments specify materials of wetted parts, meaning those that touch process fluid. There is a wide range of choices to accommodate aggressive fluids or gases. Housings also present choices, since a corrosive atmosphere in a plant can attack from the outside. Exotic materials are expensive, so choose wisely.

Internal configuration : Many sensors have internal recesses that fill with process fluid while in operation. If the fluid is benign and a small trapped amount won’t harm the product, its presence is permitted. However, some critical applications do not allow this. Sensors are available with flush diaphragms and sealed interiors to prevent infiltration of fluids and maintain minimal disruption of process flow. An isolating diaphragm also may be available as an accessory.

Process control

A differential transmitter has two inputs to compare the pressure in two vessels, but it cannot indicate the pressure against atmosphere of either side at the same time.

Housing : The safety needs of a wastewater plant differ from an oil refinery. Many options can comply with environments that demand explosion proof or intrinsically safe instrumentation. Moreover, many companies have established clear policies on what gets used and where. On the other hand, if an explosive environment isn’t a concern, the device variety available is much larger. Also, the bulkiness of the unit will depend mostly on the ancillary electronic equipment needed to communicate. A simple transducer with only a 4-20 mA output pigtail can be very compact, whereas a smart transmitter with a fieldbus connection will be larger to accommodate additional circuitry.

Mounting connection : Instruments usually have a pipe thread inlet ranging from 1/8 to 1/2 in. NPT or BSPT. However, there are additional choices for more specialized applications, including sanitary tri-clamps and other flange options. Differential pressure devices often use manifolds to simplify connections.

Communication : Most transducers transmit data using analog 4-20 mA signals. If an application uses this method, additional signal conditioning may be required to ensure reliable transmission. Transmitters also communicate via fieldbus, wireless, or HART protocols.

Sensing technology : There are about 10 technologies and variations for converting a pressure into a scalable electronic signal, but none is universal. Device manufacturers tend to employ one or two technologies following a combination of performance attributes and commercial applicability, doing their best to optimize performance and minimize drawbacks. Product literature often doesn’t even mention the technologies used. “The most critical thing is having enough experience with a given sensor technology,” says Allen Hood, product manager with ABB Instrumentation. “The standard used to be capacitance, but now there are multiple sensor technologies available because they’re optimized for the specific range. The capabilities of microprocessors in smart transmitters compensate for sensor weaknesses and allow manufacturers to concentrate on other things.”

Mounting, add-ons, maintenance

Advanced process control

This transmitter is installed with a 'gage cock,' a shutoff valve installed on a short impulse line.

Proper mounting can be as important as selecting the right device. Pressure instruments are usually mounted with a shutoff device, especially in continuous processes. That way the devices can be calibrated, repaired, or replaced while the process runs. In situations where operation is intermittent, this is not as critical, and a device can be mounted directly in the flow. A section of pipe or tubing to the sensor is called an impulse line and helps in situations where there isn’t enough room or access for the transmitter housing. However, impulse lines should be used carefully:

  • Keep them as short as possible;

  • If the process fluid is a liquid, make sure all air is bled out;

  • If you need the readout in a more convenient place, extend a cable, not the impulse line; and,

  • In high temperature situations, especially steam, ensure the impulse line can act as a siphon.

Accessories can simplify mounting, or protect the device. Here are some examples.:

Block and bleed valve —A valve mounted on the impulse line that allows pressure to be released from the sensor once the process connection is closed.

Snubber —A device to retard flow from process to sensor, primarily to suppress pulsations in an effort to extend sensor life. When properly applied, the reading is correct without harming the sensor diaphragm.

Diaphragm seal —A diaphragm mounted below the sensor to transmit pressure without allowing process fluid to infiltrate the sensor. When used, the sensor has to be filled with an inert fluid, usually a silicone oil, to transmit the system pressure.

Overpressure protector —A spring loaded valve that closes in an overpressure situation before the sensor is harmed, used where major spikes are a possibility.

Manifold —A device to simplify complex piping to a differential pressure gage, usually incorporating internal valves to facilitate cutoff, pressure relief, and equalization functions.

Maintenance and calibration requirements vary tremendously, based on the individual instrument and process needs. A quality device in an application that is of secondary importance could operate for years without attention. On the other hand, in a critical application where precision is paramount, transmitters will need periodic calibration. However, high quality transducers and transmitters receive very precise calibration at the factory, which is well beyond the capabilities of most in-plant maintenance departments. Often, attempts to improve performance only manages to make it worse. Devices from reputable manufacturers that drift or need constant attention have most likely been damaged, or are mounted in a way that hinders the ability to transmit reliable data.

Smart diagnostics

Instrumentation

Differential pressure transmitters frequently use manifolds to simplify connections. This manifold includes valves to isolate either side or equalize the internal pressure if needed. When both isolation valves are closed, the transmitter can be removed without releasing process pressure.

The term smart instrument describes a device capable of more functions than just sending a single process variable, but how does that apply to a pressure sensor? What else is there to measure?

“Whenever a failure or an event occurs that requires intervention by an operator or maintenance personnel, there is often a need to understand the cause and prevent the situation from happening again,” says Paul Schmeling, senior marketing manager, Emerson Process Management. “As instruments are the 'eyes and ears’ into the plant’s operation, there is a need to add functionality to provide greater insight into the history of the measurement or process.”

Some smart functions relate to the process and duplicate what a DCS might do, but if the instrument exists on its own, such functions can be very important. While manufacturers’ offerings differ, here are a few examples:

  • Measuring and logging over-pressure events;

  • Counting alarm and error signals;

  • Analysis of system “noise” changes signaling coming upsets;

  • Process fluid and ambient temperature measurements;

  • Self correction of the pressure value to compensate for temperature changes;

  • Self diagnostics of internal electronic functions and hardware;

  • Functionality of alarm settings; and,

  • Calibration history and schedule.

The transmitter can communicate this information using a protocol like HART or a sophisticated fieldbus. Communication can be continuous, if attached to a larger system, or via a hand-held device at given intervals.

Ultimately the best advice for selecting a pressure measuring device or any type of instrumentation, is to know the application. Knowledge of precision, communication, and diagnostics translates readily into specifications. Otherwise, pressure sensor selection could miss the mark and you’ll lose a critical element of process control.


Author Information

Peter Welander is Process Industries Editor for Control Engineering. He can be reached at PWelander@cfemedia.com .


Instrumentation nomenclature

The terms sensor, transmitter, and transducer describe different things, but their use is not always consistent and can be confusing. Here are some key, generally accepted definitions:

Sensor —The most basic device with a diaphragm and electronic components to create a raw signal. It is not sufficient to operate usefully on its own and sold primarily only to OEM’s.

Transducer —A sensor with basic electronic support to amplify and translate the raw signal into a useful format, such as 4-20 mA. A simple transducer may be all that is required if an analog process variable is sufficient for an application.

Transmitter —A sensor with more sophisticated electronic support capable of communicating the process variable in analog or digital format, either hard wired or via fieldbus.

Smart transmitter —A transmitter with additional diagnostic and supplemental variable measurement capabilities. HART-enabled transmitters are a common example.

Instrument —A less specific term that can encompass transducers, transmitters, and other devices.



No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
Each year, a panel of Control Engineering editors and industry expert judges select the System Integrator of the Year Award winners.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Learn how to create value with re-use; gain productivity with lean automation and connectivity, and optimize panel design and construction.
Go deep: Automation tackles offshore oil challenges; Ethernet advice; Wireless robotics; Product exclusives; Digital edition exclusives
Lost in the gray scale? How to get effective HMIs; Best practices: Integrate old and new wireless systems; Smart software, networks; Service provider certifications
Fixing PID: Part 2: Tweaking controller strategy; Machine safety networks; Salary survey and career advice; Smart I/O architecture; Product exclusives
The Ask Control Engineering blog covers all aspects of automation, including motors, drives, sensors, motion control, machine control, and embedded systems.
Look at the basics of industrial wireless technologies, wireless concepts, wireless standards, and wireless best practices with Daniel E. Capano of Diversified Technical Services Inc.
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
This is a blog from the trenches – written by engineers who are implementing and upgrading control systems every day across every industry.
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Control Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.