Why is improper EMI grounding so common?

Despite their demonstrated benefits, variable-frequency drives (VFDs) have a tendency to generate electrical noise (EMI) and be susceptible to interference. In a recent article, Frank Bartos explains how drive design and installation techniques can minimize EMI. Here, he discusses the importance of proper grounding and bonding.

12/18/2009


Proper grounding and bonding is a must to mitigate electromagnetic interference (EMI) in variable-frequency drives (VFDs) and electrical systems. Unfortunately, improper EMI grounding is common. Mike Olson, power & control sales manager-HVAC applications at ABB Inc ., suggests two reasons for this situation:

1. VFDs are the most EMI-prone devices that installers handle, and their routine grounding methods used with other devices are not always adequate for drives;

2. Many buildings in the U.S. don't have a good, solid common ground, placing one floor-or one side of a building-at a slightly different potential than the main ground connection in the basement. "All building grounds should be at the same potential, which is often not the case," Olson says.

Grounding effectiveness for electromagnetic compatibility (EMC) is enhanced by an added bonding component, says Olson. Electrical bonding connects metallic, non-current-carrying components at a location, placing them at the same electric potential.

Matt Murray, SEW Eurodrive 's corporate trainer, believes that proper grounding tends to be more of a problem in the U.S. than in Europe and other parts of the world. This comes, in part, from the U.S.'s relatively reliable power grid and fairly clean power, compared to other countries. It seems that belief in grid reliability is causing some electric equipment installers to not focus first on proper EMI grounding practices, says Murray.

"European equipment and drives come with extra EMI measures-and higher cost-due to generally less grid reliability," says Murray. "OEMs don't know where a system might end up being used when they're designing it. This is the main reason for the increased measure of EMI protection included in a system. It includes filters, output chokes, and importantly, proper grounding for EMC."

Another part of the answer is that, currently, there is no binding EMC regulation for electric drives in the U.S. As a result, not all equipment installers are fully aware of EMC requirements.

To read the entire article, " Electromagnetic Interference: What Users of Drives Need to Know ," visit www.controleng.com/archive under Dec. 2009.

Also see: " Silence of the Drives " under June 2008
Frank J. Bartos, P.E, consulting editor, braunbart@sbcglobal.net

Separating different cable types is a prudent EMC measure. SEW Eurodrive recommends 10 cm (4 in.) spacing between cable groups I and II; 20 cm between groups II and III and between groups III and IV.





No comments
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
The System Integrator Giants program lists the top 100 system integrators among companies listed in CFE Media's Global System Integrator Database.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
This eGuide illustrates solutions, applications and benefits of machine vision systems.
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Salary and career survey: Benchmarks and advice; Designing controls; Remote data collection, historians; Control valve advances; Hannover Messe; Control Engineering International
System integration: Best practices and technologies to help; Virtualization virtues; Cyber security advice; Motor system efficiency, savings; Product exclusives; Road to Hannover
Collaborative robotics: How to improve safety, return on investment; Industrial Internet of Things, Industrie 4.0: World views; High-performance HMI, Information Integration: OPC and OMG
This article collection contains several articles on the Industrial Internet of Things (IIoT) and how it is transforming manufacturing.
PLCs, robots, and the quest for a single controller; how OEE is key to automation solutions.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

Getting to the bottom of subsea repairs: Older pipelines need more attention, and operators need a repair strategy; OTC preview; Offshore production difficult - and crucial
Digital oilfields: Integrated HMI/SCADA systems enable smarter data acquisition; Real-world impact of simulation; Electric actuator technology prospers in production fields
Special report: U.S. natural gas; LNG transport technologies evolve to meet market demand; Understanding new methane regulations; Predictive maintenance for gas pipeline compressors
click me