Use thermocouple tech to achieve reliable multipoint temperature profiling
Advanced temperature measurement technology for cleaner, safer and more profitable downstream operations depends on reliable thermocouple technology
In the refining industry, catalytic hydroprocessÂing elements, such as hydrotreater, hydrodeÂsulfurization and hydrocracker units, rely on high-performance catalyst technologies to maximize product conversion (see Figure 1). Simultaneously, efficient reaction control seeks to minimize the environmental footprint and cost. Precise and reliable temperature mapping of these densely packed reactor catalyst beds is required for stable and profitable unit operations. Multipoint temperature instruments with thermocouple sensors are widely used in the industry to monitor for optimum heat distribution, and to prevent hotspots and premature catalyst deactivaÂtion under high temperature, high pressure and corrosive conditions.
However, most conventional multipoint thermoÂcouple probe designs have two major weaknesses:
• Reliability: Hydrogen sulfide (H2S) contaminaÂtion affects conventional magnesium oxide (MgO) cables under extreme process conditions. H2S contamination can alter measurement accuracy or even lead to a loss of control over the reaction.
• Size: They are comparatively invasive, taking up valuable space in catalyst beds, leading to undesired pressure drops and channeling effects.
A new multipoint thermocouple probe design addresses these issues by combining thermowell and thermocouple sensors in a single space-saving probe, addressing failure vulnerabilities while providing more efficient catalytic reaction. The patented technology helps the automation system provide more reliable, precise and accurate process control, directly conÂtributing to improved safety, profitability and uptime.
Thermocouple drift and migration
The harsh environments typically encountered in catalytic hydrocracker units pose a difficult chalÂlenge for process instrumentation. While all therÂmocouple probes are known to drift over time, mechanical stress, abrasion and H2S contamination are often not factored in when specifying design limits and making instrument vendor selections. Unfortunately, these issues can lead to a total loss of data, threatening process safety, reaction control and efficiency.
In these types of applications, industry expectaÂtions of a multipoint temperature instrument’s usable life for its wetted parts are typically one- or two-unit operation cycles or turnarounds, or 36 to 48 months. As the industry changes, there are desires for even longer life cycles of five to seven years, prompting increased demand for longer instrumentation and equipment life cycles.
Defective thermocouple probes have been found in a significant number of applications throughÂout the industry and are systematically affecting all instrument manufacturers. This occurrence has been examined scientifically, resulting in the discovÂery of two phenomena that degrade thermocouple measurement performance, with each occurring separately or in combination:
- Thermocouple drift. Chemical contamination of the MgO powder induces a change in the composition of the two dissimilar metals that make up the thermocouple conductor wires, leading to a shift in potential difference due to the Seebeck or thermoelectric effect. While the local hot junction remains intact, a change in conductivity of one or both metals will alter the measured voltage and negatively impact meaÂsurement accuracy.
- Hot junction migration. Permeation of H2S into the MgO powder can cause new conductive bonds (electrical short circuits) to form between the thermocouple wires at undesired locations away from the hot junction. The thermocouple will still work but will present incorrect values that seem true.
If one or several defective thermocouple sensors have been identified, process owners might decide to address the issue during the next scheduled unit turnaround. Depending on the severity of the failÂures and their safety criticality, extraordinary mainÂtenance for sensor replacement might be required, which could entail an unscheduled unit shutdown.
H2S contamination and thermocouple technology
Sensor drift or damage causes erroneous readings that may go undetected by operation and process control staff. This scenario is particularly dangerous because misinformation or a lack of information in the meaÂsurement chain can lead to operational decisions with poor outcomes for reaction efficiency or worse.
According to technical investigations and relevant scientific literature, deviations in measurement accuÂracy (drift) of contaminated thermocouple sensors is typically negative. Therefore, the value displayed will be lower than the actual temperature, and the proÂcess may be running hotter than intended. Besides being a major cost issue, such an out-of-spec state poses a considerable safety threat.
Legacy designs assume that sensors protected by singular MgO insulation provide sufficient measureÂment accuracy and precision. However, these standard multipoint thermocouple probes have been known to fail under more challenging process conditions.
Hydrogen stress-induced cracking in thermocouple conductors
It is standard practice to bend and route sensor cable probes inside a reactor to match the required layout because this flexible installation method ensures measurement points are adequately distributed. However, the bending of metal induces expansion and compression stress, causing weak spots, parÂticularly along sharp bends.
In hydrogen-rich atmospheres, hydrogen stress-induced cracking may occur at these weak spots, which in time can increase enough to break through the metal sheath entirely. This loss of integrity leads to larger molecules of the process fluid, such as H2S, permeating through and contaminating the insulating MgO powder.
MgO powder reacts with certain chemicals, including sulfur and nickel. The now contaminated MgO powder promotes the formation of highly conÂductive Ni3S2 by combining nickel from the thermoÂcouple conductor leads and the metal sheath with sulfur from the process.
As the contaminated area grows, the exposed elecÂtrical leads form a short circuit, negatively impactÂing sensor accuracy or migrating the location of the thermocouple hot junction. The complete probe risks becoming blind to process temperature changes.
Temperature sensor designs address issues
The minimally invasive Endress+Hauser iTHERM ProfileSens TS901 multipoint cable probes consist of two or more independent temperature sensors embedded in a common outer metallic sheath. The outer sheath acts as an integrated thermowell while the space between the sensors is filled with highly compacted insulating MgO mineral powder (see Figure 2).
Since the two sensors are completely independent from each other, contamination of the outer MgO powder does not affect the inner sensors’ electrical circuits and their operation. New, patented techÂnology introduces a second layer of protection. An additional metal barrier isolates each measuring circuit within its own MgO bed, providing full sensor independence. This double protection layer results in high sensor reliability, similar to a separate therÂmowell, while maintaining the flexibility characterÂistics of bendable cable probes.
Multiple thermocouple sensors can be grouped within a single probe, each delivering the required measurement performance. The probe layout and routing, length and the number of sensors is indiÂvidually adapted to process specifications. This type of design is proven in use to lower the risk of preÂmature sensor drift, corrosion and short circuits.
Spatial footprint impacts product conversion
Reducing space taken up by invasive reactor instruÂmentation is an evident way to increase conversion rate and productivity. The amount of necessary hardÂware directly impacts the catalyst charge density. Three key factors influence the spatial footprint:
- Probe design
- Sensor routing
- Mounting hardware.
Probe design. Standard multipoint thermocouple probe technology has long been considered mature, but recent research efforts have re-evaluated the mechanical design. This led to the use of advanced manufacturing processes to add safety layers and significantly miniaturize MgO cables, without compromising their existing qualities. The gain in robustness and spatial volume translates into a better use of catalyst bed packing. By simply reducing the number of thermocouple cables across the reactor bed, negative effects are also reduced, improving catalyst reactivity and profitability.
Sensor routing. Through smart sensor routing, measurement points can be distributed in the most effective way, while reducing the overall invasiveÂness. State-of-the-art CAD modeling software and routing calculations are used by seasoned engineers, applying years of experience in reactor layout to achieve best results.
Mounting hardware. Placing multipoint therÂmocouple probes in reactor beds typically requires mounting hardware, adding to the overall spatial footprint of the instrument. However, new cable probe technology factors in this requirement and reduces the number of brackets and mounting clips. The probe mechanical structure provides a higher degree of self-support for the cable, resulting in fewer required supporting elements, while remainÂing bendable. This reduces the instrument footprint while cutting overall hardware cost and installation time. The higher product conversion, yield and proÂcess efficiency quickly offsets the initial investment.
Return on investment
In addition to improved process safety, control and reliability, this technology unlocks profitability potential by:
- Saving space for a higher catalyst charge density
- Preventing untimely shutdowns or required maintenance caused by instrument failure
- Allowing operation of units closer to their perÂformance optimum.
To demonstrate how much impact a less invaÂsive instrument can have on profitability, consider a typical hydrocracker reactor with three catalyst beds. Each bed is equipped with one entry nozzle and twelve measurement points.
Standard multipoint instruments would use:
- Twelve 8-mm thermocouples and probes per bed
- One thermocouple sensor per cable, for a total of 12 cables
- Average length of 8 m.
New design uses:
- Three 9.5-mm multipoint cable probes per bed, each with four thermocouple sensors per probe, for a total of nine cables
- Up to 13-m length.
The newer design increases the usable catalyst bed volume by 50% and cuts installation time by 75%. The increased volume can be used to boost the catalyst load, and the saved installation time directly translates into quicker turnarounds and lower cost.
Measured against an average daily unit profitabilÂity and a continuous operation of 36 to 48 months, the resulting extra revenue generated fully offsets the capital expenditure (CapEx) (see Figure 3).
With iTHERM ProfileSens, the initial CapEx (left y axis, base 100: standard multipoint installation), while minimally higher, is quickly offset through higher yield (right y axis, base 100: standard mulÂtipoint installation) and savings. The major factors leading to this quick return on investment are:
- Higher unit performance and conversion
- Higher efficiency
- Faster installation and turnaround
- Lower operational expenditure (OPEX).
As the number of measurement points increase, the savings effect grows to the point where the initial investment becomes negligible when compared to the increased returns. The new technology’s robustÂness, reliability and longer operating life makes it a compelling choice for harsh process conditions.
Final thoughts
While drifting thermocouple measurements are a known phenomenon, the underlying causes of senÂsor misbehavior beyond typical drift are still widely unknown to many refinery operators. Migrating hot junctions go undetected in most cases, leaving proÂcess control engineers unaware of the lost potential.
Extensive tests and scientific studies have shown that mechanical stress, abrasion, corrosion, hydroÂgen stress-induced cracking and subsequent H2S contamination is a leading cause for total loss of data, reducing process efficiency, while posing risks to safety and reaction control. The iTHERM ProfileSens addresses these issues to provide improved proÂcess safety, control and reliability. It also unlocks hidden profitability potential, offering refiners a smart choice to get the most out of new or existing units.
Original content can be found at Plant Engineering.