Facility Focuses on Motors to Prevent Energy Waste
Sheboygan Regional Wastewater has five remote wastewater pumping stations throughout the city of Sheboygan, WI. These pumping stations are monitored remotely with a SCADA system that does not monitor motor load conditions. Therefore, maintenance personnel routinely go 30 ft. below ground to check the health of the pumps and motors.
Sidebars: 50 million tons of emissions reductions Wireless technology monitors energy Switch auto-manages its power usage
Sheboygan Regional Wastewater has five remote wastewater pumping stations throughout the city of Sheboygan, WI. These pumping stations are monitored remotely with a SCADA system that does not monitor motor load conditions. Therefore, maintenance personnel routinely go 30 ft. below ground to check the health of the pumps and motors.
“The average daily flow at the facility is about 11 million gallons,” explains Dale Doerr, Sheboygan Regional Wastewater superintendent. “If we have a rain event or substantial snow melt, we can reach peak flows of 64 million gallons. This makes it essential for all our pumps to operate at capacity, to ensure that we can manage the increased flow levels and avoid adverse sewer problems for the 68,000 people we serve.”
With its pumps typically located 30 ft. below ground, Sheboygan Regional Wastewater monitored its pumping stations remotely with a SCADA system, but the system was unable to detect motor load conditions.
If a pump is partially restrained, the pump and motor would still run, albeit inefficiently, until the bi-metallic overloads eventually trip. This happens if current draw is sustained at a level above 115% full load amperage (FLA) for a period of time.
Lift station retrofit
With this motor issue in mind, Doerr looked into using Eaton’s Motor Insight overload relay. Eaton explained that these relays would allow Sheboygan Regional to monitor its entire system including line, load, and motor from a headquarters location, thus avoiding the manual pump checks. With real-time data, maintenance personnel would only need to be sent to a location when data suggested there was a problem.
Sheboygan Regional agreed to be a beta site and retrofit its Indiana Avenue lift station with Motor Insight relays, remote displays, and Modbus communication modules on the station’s three 60 hp pump motors.
Impact of early detection
Soon after installing the devices, maintenance personnel noticed a problem with one of the pumps. While two pumps were drawing around 60 amps when flow was at its maximum level, the third pump was drawing closer to 90 amps. Sheboygan Wastewater’s maintenance supervisor immediately noticed this higher current level and dispatched a maintenance technician, who then found a foreign object wrapped around the impeller of the third pump.
For Sheboygan Regional, it is critical that all the pumps are able to function at capacity to make sure that flow levels can be managed to avoid severe problems.
“Prior to the Motor Insight installation, the issue may have never been noticed because the facility only looked at its flow meter, which reports gallons per minute,” says Steve Meifert, Sheboygan Regional Wastewater controls engineer. He noted that the flow was still the same for all three pumps.
In addition, Meifert noted that the increase in current caused by the obstruction may not have been large enough to trip the previously used bi-metallic overloads. Thus, the extra power draw could have gone on for an extended period of time without being detected, leading to large energy losses.
Meifert explains that, from a cost standpoint, had this problem gone unnoticed, it would have equated to: 30 amps x 480V = 14,400 Watt-hours or 14.4 kW-hrs x $0.104/kw-hr or to $1.50/per hour of unnoticed run time. If this condition had gone unnoticed for an extended period of time, this could amount to $252 in wasted energy for one week ($1.50 x 24 x 7 =$252); $1,096 of wasted energy for one month; and $13,154 in wasted energy over a year.
The facility is currently using Motor Insight to monitor volts, amps, thermal capacity, frequency, power, and power factor. It has set alarm levels for overcurrent and undercurrent, and set a displayed fault for an overload condition. If the situation had been a more severe deviation from the normal operating conditions, the Motor Insight’s load, line, or motor protection settings would have created a fault to protect the system.
An optional remote display eliminates the need to open the panel to configure the device. External interface is the same as on the base unit device (shown at the bottom of this composite photo). Source: Eaton
Preventing equipment failure
In another instance, Motor Insight paged out an alarm of an undercurrent over the weekend. Maintenance personnel investigated, and found and removed a blockage in the check valve. Without Motor Insight, this issue would not have been detected until the next week when staff looked at the flow charts and realized that, when the pump was running, there was either no flow or only a partial flow.
Doerr said, “If the problem was not detected until Monday or Tuesday, you could possibly have a second pump come on to compensate, which would mean additional energy costs. Although pumps can run with a valve closed, the pumps can heat up, damaging the mechanical seals that rely on water as a cooling agent. This happens when the overheated pump heats up the water because there is nowhere for it to go, therefore it cannot cool the unit. The mechanical seal can then be damaged and lead to about $1,000 in repair cost, in addition to the cost of wasted energy.
“We now have the ability to find and resolve a situation before it becomes a failure,” Meifert says. “For a bi-metallic to trip, an object like a piece of wood or chunk of asphalt would have to wedge in the sidewall of the pump. Since the motor would not be able to turn in that case, it would overload. To fix the problem, you cannot just go to the location and remove an inspection cover and remove the obstruction. You have to disassemble the motor and impeller, remove the foreign object and then reassemble the entire unit.”
Doerr adds, “With Motor Insight’s ability to monitor the pump motors and loads in our hard-to-access areas, Sheboygan now has the ability to trend motor conditions in real time that could have gone unnoticed for days and even weeks. The Motor Insight overload and monitoring relay allows us to send out maintenance personnel when a problem occurs, potentially saving us thousands of dollars annually.”
Sheboygan Regional retrofitted its Indiana Avenue lift station with Motor Insight relays, remote displays and Modbus communication modules on three 60 hp motors. Source: Eaton
Author Information
Adam Krug is product manager of power protection at Eaton. For more information, visit
50 million tons of emissions reductions
In April, some of the world’s leading companies, all partners in the World Wildlife Federation’s Climate Savers Program, announced substantial voluntary emissions reductions — equivalent to the annual emissions of Switzerland — by 2010.
Wireless technology monitors energy
The cost of traditional wired sensing systems can erase much or all of the financial gains of greater energy efficiency. An article series explains why, and how the solution may be wireless monitoring. Search “wireless” at www.controleng.com
Switch auto-manages its power usage
The D-Link Green 16-port Managed Gigabit Switch for Ethernet is said to automatically detect device link status and reduce power usage of ports that are not linked, which can save up to 14.28% of power without affecting network performance.
Do you have experience and expertise with the topics mentioned in this content? You should consider contributing to our WTWH Media editorial team and getting the recognition you and your company deserve. Click here to start this process.