Seat leakage classifications
Seat Leakage Classifications (In accordance with ANSI B16.104-1976)
Leakage class designation
Maximum leakage allowable
Test medium
Test pressure
Testing procedures required for establishing rating
I
—
—
—
No test required provided user and supplier agree.
II
0.5% of rated capacity
Air or water at 50 to 125
45 to 60 psi (3.1 to 4.1 bar) or maximum operating differential whichever is lower
Pressure is applied to valve inlet, with outlet open to atmosphere or connected to a low head-loss measuring device, full normal closing thrust provided by actuator.
III
0.1% of rated capacity
As above
As above
As above
IV
0.01% of rated capacity
As above
As above
As above
V
0.0005 liters per minute of water per inch (mm) of port diameter per psi (bar) differential.
Water at 50 to 125
Maximum service pressure drop across valve plug, not to exceed ANSI body rating. 100 psi (6.9 bar) pressure drop minimum.
Pressure applied to valve inlet after filling entire body cavity and connected piping with water and stroking valve plug closed. Use net specified maximum actuator thrust, but no more, even if available during test. Allow time for leakage flow to stabilize.
VI
Not to exceed amounts shown in Class VI Seat Leakage Allowance table based on port (orifice) diameter.
Air or nitrogen at 50 to 125
50 psig (3.4 bar) or maximum rated differential pressure across valve plug, whichever is lower.
Actuator should be adjusted to operating conditions specified with full normal closing thrust applied to valve plug set. Allow time for leakage flow to stabilize and use suitable measuring devices.
Source: Control Engineering with data from Fisher Controls.
Class VI Seat Leakage Allowance
Nominal port diameter
Leak Rate
Inches
Millimeters
ml per minute
Bubbles per minute (1)
1.5
38
0.30
2
2
51
0.45
3
2.5
64
0.60
4
3
76
0.90
6
4
102
1.70
11
6
152
4.00
27
8
203
6.75
45
1. Bubbles per minute as tabulated are an easily measured suggested alternative based on a suitable calibrated measuring device such as aary from those shown, as long as they correctly indicate the flow in ml per minute.
Source: Control Engineering with data from Fisher Controls
Comments?E-mail dharrold@cahners.com
Do you have experience and expertise with the topics mentioned in this content? You should consider contributing to our WTWH Media editorial team and getting the recognition you and your company deserve. Click here to start this process.