Tuning PID control loops for fast response

When choosing a tuning strategy for a specific control loop, it is important to match the technique to the needs of that loop and the larger process. It is also important to have more than one approach in your repertoire, and the Cohen-Coon method can be a handy addition in the right situation.


The well-known Ziegler-Nichols tuning rules work well only on processes with very long time constants relative to their dead times, and on level control loops. However, its performance is not good on flow, liquid pressure, and many other loops that require fast adjustment. In contrast, the Cohen-Coon tuning rules work well on virtually all self-regulating processes and were designed to give a very fast response.

The method's original design resulted in loops with too much oscillatory response and consequently fell into disuse. However, with some modification, Cohen-Coon tuning rules proved their value for control loops that need to respond quickly while being much less prone to oscillations.

Applicable process types

The Cohen-Coon tuning method isn't suitable for every application. For starters, it can be used only on self-regulating processes. Most control loops, e.g., flow, temperature, pressure, speed, and composition, are, at least to some extent, self-regulating processes. (On the other hand, the most common integrating process is a level control loop.)

Figure 1: Step test for Cohen-Coon tuning. Courtesy: DataforthA self-regulating process always stabilizes at some point of equilibrium, which depends on the process design and the controller output. If the controller output is set to a different value, the process will respond and stabilize at a new point of equilibrium.

Target controller algorithm

Cohen-Coon tuning rules have been designed for use on a non-interactive controller algorithm such as that provided by the Dataforth MAQ 20 industrial data acquisition and control system. There are controllers with similar characteristics available from other suppliers.


To apply modified Cohen-Coon tuning rules, follow the steps below. The process variable and controller output must be time-trended so that measurements can be taken from them.

1. Do a controller output step test:

  • Put the controller in manual and wait for the process to settle out.
  • Make a step change in the CO (controller output) of a few percent and wait for the PV (process variable) to settle out. The size of this step should be large enough that the PV moves well clear of the process noise and disturbance level. A total movement of five times more than the peak-to-peak level of the noise and disturbances on the PV should be sufficient.

Figure 2: A temperature control loop, tuned with modified Cohen-Coon method, responding to a set point change. Courtesy: Dataforth2. Determine the process characteristics (see Figure 1):

  • If the PV is not ranged 0-100%, convert the change in PV to a percentage of the range: change in PV [in %] = change in PV [in engineering units] × 100 / (PV upper calibration limit - PV lower calibration limit).
  • Calculate the process gain (gp): gp = total change in PV [in %] / change in CO [in %].
  • Find the maximum slope of the PV response curve. This will be at the point of inflection. Draw a tangential line through the PV response curve at this point.
  • Extend this line to intersect with the original level of the PV before the step in CO.
  • Take note of the time value at this intersection and calculate the dead time (td): td = time difference between the change in CO and the intersection of the tangential line and the original PV level.
  • If td was measured in seconds, divide it by 60 to convert it to minutes. (Since the Dataforth PID controller uses minutes as its time base for integral time, all measurements have to be made in minutes or converted to minutes. Many other controllers are similar.)
  • Calculate the value of the PV at 63% of its total change.
  • On the PV reaction curve, find the time value at which the PV reaches this level.
  • Calculate the time constant (t): t = time difference between intersection at the end of dead time and the PV reaching 63% of its total change.
  • If t was measured in seconds, divide it by 60 to convert it to minutes.

3. Repeat steps 1 and 2 three more times to obtain good average values for the process characteristics.

4. Calculate controller settings for a PI or PID controller using the modified Cohen-Coon equations below. (The modified rules calculate the controller gain as ½ of that calculated by the original rules.) 

5. Enter the values into the controller, make sure the algorithm is set to non-interactive, and put the controller in automatic mode.

6. Change the setpoint to test the new values.

Do fine tuning if necessary. The control loop's response can be slowed down and made less oscillatory, if needed, by decreasing KC and/or increasing TI.


These modified Cohen-Coon tuning rules are an excellent method for achieving fast response on virtually all control loops with self-regulating processes. They are an effective and highly reliable alternative to the Ziegler-Nichols tuning method, which does not work well when applied to many self-regulating processes.

Lee Payne is CEO of Dataforth.

Additional reading: G.H. Cohen and G.A. Coon, Theoretical Consideration of Retarded Control, Trans. ASME, 75, pp. 827-834, 1953.


To learn more about PID, look for additional application notes at the Dataforth website: www.dataforth.com 

Read more about PID control and loop tuning below.

Key concepts

  • Cohen-Coon tuning rules are effective on virtually all control loops with self-regulating processes.
  • They are designed for use on a noninteractive controller algorithm.
  • The modified Cohen-Coon method provides fast response and is an excellent alternative to Ziegler-Nichols for self-regulating processes.


Mustafa , AK, Turkey, 07/04/14 02:36 AM:

Very useful for me to understand self-regulating process.
Anonymous , 07/05/14 06:09 AM:

The topic is very useful for tuning a controller.
Anonymous , 07/07/14 09:14 AM:

very interesting
JOHN , IL, United States, 07/11/14 02:18 PM:

Dear Lee,
I don't mean to be pedantic, but .... You said, "A self-regulating process always stabilizes at some point of equilibrium, ... the process will respond and stabilize at a new point of equilibrium."
Equilibrium is better used to describe how complete a chemical reaction is. Self regulating processes should be referred to as reaching steady state. For example, if you are scrubbing a gas stream with a liquid in a tower, the process may be working fine if the streams have reached steady state. But if the passing streams are in equilibrium, the process has failed, as no absorption occurs at equilibrium. So talking about reaching "steady state" would have been a much better choice in your article than talking of an "equilibrium".
Grace and Peace,
SALAHUDDIN , NJ, United States, 07/11/14 03:12 PM:

Never tried Cohen-Coon rules in this plant.This seems to be very interesting. I will try on a few loops. Will keep everybody updated
Marcos , Non-US/Not Applicable, Mexico, 07/11/14 03:31 PM:

Hi, i would like to know where can i get Dataforth products here in Mexico.
Marcos Rivera Avila
Anonymous , 07/13/14 12:37 AM:

It is very good information.
ANTHONY , TX, United States, 08/08/14 01:08 PM:

Cohen-Coon is only offline method and for first-order process only.

For second-order and fast response tuning, consider Lambda tuning as an alternative.
Eduardo , Non-US/Not Applicable, Mexico, 08/10/14 09:15 AM:

Mr Lee. I´m, in according with you, don´t import the form of words,"self-regulating process always stabilizes or point of equilibrium"; the very important is the Concept, and your application is very good. the Dead time is not always Dead in the process.. thank E.Z.U.
The Engineers' Choice Awards highlight some of the best new control, instrumentation and automation products as chosen by...
The System Integrator Giants program lists the top 100 system integrators among companies listed in CFE Media's Global System Integrator Database.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
Learn how to increase device reliability in harsh environments and decrease unplanned system downtime.
This eGuide contains a series of articles and videos that considers theoretical and practical; immediate needs and a look into the future.
Learn how to create value with re-use; gain productivity with lean automation and connectivity, and optimize panel design and construction.
Machine design tips: Pneumatic or electric; Software upgrades; Ethernet advantages; Additive manufacturing; Engineering Leaders; Product exclusives: PLC, HMI, IO
Industrial wireless cyber security: More complex than black and white; IIoT at the I/O level; Process modeling; Cyber security research
Robotic advances: Software, form factors; System-based ROI; Embedded control; MES and information integration; SCADA and cyber security; Position sensor; Controller, I/O module
Learn how Industry 4.0 adds supply chain efficiency, optimizes pricing, improves quality, and more.

Find and connect with the most suitable service provider for your unique application. Start searching the Global System Integrator Database Now!

Drilling for Big Data: Managing the flow of information; Big data drilldown series: Challenge and opportunity; OT to IT: Creating a circle of improvement; Industry loses best workers, again
Pipeline vulnerabilities? Securing hydrocarbon transit; Predictive analytics hit the mainstream; Dirty pipelines decrease flow, production—pig your line; Ensuring pipeline physical and cyber security
Cyber security attack: The threat is real; Hacking O&G control systems: Understanding the cyber risk; The active cyber defense cycle