VFD component and technology advances

Variable frequency drive (VFD) technology has progressed from bulky silicon-controlled rectifier (SCR)-based designs to advanced insulated gate bipolar transistor (IGBT) topologies, improving efficiency, control, and harmonic mitigation through innovative techniques that meet modern IEEE 519 standards.

  • Understand the evolution of VFD technology
  • Identify harmonic distortion issues and mitigation techniques
  • Learn different VFD topologies and their applications

VFDs have undergone significant advancements since their introduction in the late 1950s. Early VFDs relied on silicon-controlled rectifiers (SCRs), which were first introduced in 1957. These devices allowed for basic control of alternating current (AC) motor speed by rectifying incoming AC voltage and switching it through a gate signal. However, early SCR-based drives were bulky, expensive, and limited in performance, making them suitable only for select industrial applications.

To improve controllability, gate turn-off thyristors (GTOs) were developed in the 1960s. Unlike SCRs, GTOs could be turned off via a gate signal, allowing for more precise control of motor operation. Despite this improvement, GTOs required high gate currents and had slower switching speeds, which limited their use in high-performance applications. These early drives typically used six-step inverter technology and were classified as either variable-voltage inverters or current-source inverters. While they provided basic speed control, they also introduced significant waveform distortion and required large enclosures due to cooling equipment and component size.

The introduction of pulse-width modulation (PWM) in the mid-1960s marked a turning point in VFD design. PWM allowed for smoother motor voltage output by modulating the width of voltage pulses to simulate a sinusoidal waveform. This technique improved motor performance and reduced torque ripple. However, early PWM drives still relied on bipolar transistors and were limited by switching speed and efficiency.

The development of insulated gate bipolar transistors (IGBTs) in the early 1980s revolutionized VFD technology. IGBTs combined the high-current capability of bipolar transistors with the easy gate control of metal-oxide-semiconductor field-effect transistors (MOSFETs), enabling high-speed switching and compact drive designs. By the late 1980s, IGBT-based PWM drives became the industry standard, offering improved efficiency, reduced size and lower cost. These drives could operate at ultrasonic switching frequencies (10 to 15 kilohertz), resulting in smoother motor operation and quieter performance. The widespread adoption of IGBT technology also enabled the integration of advanced control algorithms, such as vector control and direct torque control, further enhancing drive capabilities.

In the early 2000s, matrix VFDs emerged as a new topology that eliminated the traditional direct current (DC) bus. Instead of converting AC to DC and back to AC, matrix drives perform direct AC-to-AC conversion using nine bidirectional IGBTs (18 IGBTs total) arranged in a matrix configuration. This design allows any input phase to connect to any output phase at any time, resulting in a naturally sinusoidal input waveform. Matrix VFDs also support regenerative braking and offer high efficiency, as only six IGBTs are actively switching at a time and no additional components, like braking resistors or inductor-capacitor-inductor (LCL) filters, are required. While a limited number of manufacturers currently produce matrix drives, they represent a promising advancement in VFD technology, particularly for applications requiring compact design and low harmonic impact.

Harmonic mitigation advances

VFDs are nonlinear loads and, therefore, create harmonic waveforms and introduce them into the electrical system. Harmonics are unwanted waveforms with a frequency that is a multiple of the fundamental frequency. They cause current and voltage distortion within the electrical system, leading to a non-sinusoidal waveform. Harmonics can lead to breaker nuisance tripping, equipment overheating, premature motor and cable failures, and malfunction of sensitive electronics, among other things. Because of these issues, Institute of Electrical and Electronic Engineers (IEEE) 519, Recommended Practices and Requirements for Harmonic Control in Electric Power Systems, was introduced in 1981 to set limits on harmonic distortion in electrical systems. Although this document is technically a guideline, it has been enforced by electric utility companies and energy codes, essentially forcing manufacturers to implement several techniques to mitigate the harmonics over the years.

Figure 1: A 6-Pulse VFD is shown with an internal line reactor; line reactors are better for lower-horsepower (hp) motors (below 30 to 50 hp) or need to be paired with other harmonic mitigation techniques to further reduce the distortion levels. Courtesy: CDM Smith

Line-side harmonic mitigation techniques

The simplest and most cost-effective form of harmonic mitigation is the line reactor. A line reactor is an inductor placed on the line side of a VFD. They usually come in two forms, 3% and 5% impedance, with higher impedance providing better harmonic mitigation. However, line reactors typically can only reduce high levels of harmonic distortion created by the VFD (roughly 80%) down to 30% to 40%. Therefore, line reactors are better for lower-horsepower (hp) motors (below 30 to 50 hp) or need to be paired with other harmonic mitigation techniques to further reduce the distortion levels (Figure 1).

In the 1980s and 1990s, multi-pulse VFDs gained popularity as the need to further reduce harmonic distortion caused by 6-pulse VFDs increased. Multi-pulse VFDs were created by adding a phase shifting transformer to the input of the VFD. Phase-shifting transformers have multiple secondary windings, allowing for connection of more diodes (six per secondary winding) in the rectifier section of the VFD.

Phase-shifting VFDs, two varieties

Two main varieties of phase-shifting VFDs were developed for low-voltage VFDs: 12-pulse and 18-pulse designs. For a 12-pulse VFD, the phase-shifting transformer has two three-phase secondary windings that are phase-shifted 30 degrees from each other, allowing for two sets of six diode bridges to operate in parallel. This setup would create double the amount of voltage pulses on the DC bus, providing a smoother DC waveform, which leads to overall better VFD performance and cleaner output for the motor. Also, the phase shifting helps to cancel out lower-order harmonics, namely the fifth and seventh, thus reducing total harmonic distortion (THD) down to 12% to 20%. However, while the 12-pulse VFD further improved upon a 6-pulse VFD, it was large and expensive, and it still fell short of the harmonic distortion limits set forth in IEEE 519 (1992 version), leading to obsoletion in the early 2000s.

Figure 2: Phase shifting transformer is shown for an 18-pulse VFD. The 18-pulse VFD offered superior harmonic mitigation, with marginally higher costs, over the 12-pulse VFD, often meeting IEEE 519 limits by getting the THD down to 5% or lower. Courtesy: CDM Smith

The need to further improve upon the harmonic distortion led to the introduction of the 18-pulse VFD. This design expands on the 12-pulse VFD by adding another three-phase secondary winding to the phase shifting transformer (with a phase shift at 20 degrees), allowing for three sets of six diodes in the rectifier section. This created an even smoother DC bus and canceled out even more harmonics, namely the 5th, 7th, 11th, and 13th. The 18-pulse VFD offered superior harmonic mitigation, with marginally higher costs, over the 12-pulse VFD, often meeting IEEE 519 limits by getting the THD down to 5% or lower. These VFDs became the dominant VFD used for larger motors (50 to 100 hp and larger) for many years. While the 18-pulse VFD is still in use today, the advancement of technology has given rise to other low harmonic solutions, such as passive harmonic filters (PHF), active front-end (AFE) VFDs, and matrix VFDs (Figure 2).

Figure 3: Passive harmonic filter is shown inside 6-pulse VFD enclosure. These filters have created a cost-effective alternative to 18-pulse VFDs or AFE VFDs and can be used for both low hp and very large hp (500+) motors Courtesy: CDM Smith

The PHF is not a VFD itself but a harmonic filter added to the line side of a 6-pulse VFD to create a complete package. A PHF consists of inductors and capacitors configured in either series or parallel. The inductors work by blocking the high-frequency harmonics while the capacitors provide a low-impedance path for the harmonic currents and remove them from the system. PHFs can either be tuned for certain harmonic orders, such as the fifth or seventh, or provide broad protection for several harmonic orders. PHFs can typically reduce THD below 5%, usually meeting IEEE 519 guidelines. These filters have created a cost-effective alternative to 18-pulse VFDs or AFE VFDs and can be used for both low hp and very large hp (500+) motors (Figure 3).

AFE VFDs take the concept of a 6-pulse VFD but swap out the uncontrolled diode rectifier with six IGBTs, or other controllable transistors, similar to what is in the inverter section. This allows the rectifier section to also have PWM switching, allowing the VFD to draw nearly sinusoidal current from the power source, minimizing harmonic distortion. An AFE VFD also integrates an inductor-capacitor-inductor (LCL) filter on the line side of the VFD to further smooth out the waveform. While these VFDs have been around since the late 1990s and early 2000s, it was not until recently that many manufacturers have decided to discontinue their 18-pulse VFD lines in favor of AFEs. These VFDs easily meet IEEE 519 guidelines by reducing THD below 5%, often as low as 2% to 3%. Because of cost, the application of these VFDs is typically above 100 hp.

As previously mentioned, matrix VFDs use a different design topology compared to the other VFDs mentioned in this article. The use of nine bidirectional IGBTs and elimination of the DC bus allows the input waveform to be naturally sinusoidal, leading to low levels of harmonics (typically 3% to 5% THD). While matrix VFDs are available for motors as low as 5 hp, the harmonic mitigation benefits do not outweigh the cost below 100 hp, as options like a 6-pulse VFD paired with a line reactor or PHF are more cost-effective at lower hps.

Load-side harmonic mitigation techniques

VFDs also create voltage issues at the VFD output because of the high switching frequency of the IGBTs. The rapid switching causes a high rate of voltage change over time (dv/dt) and, therefore, a high rate of current change over time (di/dt). Because of the inductance (L) in cables and motor windings, the output voltage delivered to the motor is increased because of the following equation:

V = L × di/dt

Also, a phenomenon called reflected wave, because of impedance differences in the motor and cables, causes the voltage to reflect back to the VFD, resulting in doubling the output voltage. These high voltage levels can cause arcing across motor windings, leading to insulation damage and shortening the motor lifespan. High voltage levels can also do the same thing to cables. Keeping cable lengths as short as possible (less than 50 to 100 feet) helps to mitigate these issues; however, this is not always possible.

Figure 4: A dv/dt filter combines inductors, capacitors, and resistors to decrease voltage spikes and filter out fast transients from the circuit. DV/DT filter is shown inside VFD enclosure. Courtesy: CDM Smith

Three VFD devices to mitigate voltage spikes

The following devices can be integrated into VFDs to help mitigate these voltage spikes:

  • Load reactors are a simple, cost-effective device (similar to line reactors) that can be placed on the output of a VFD. They slow down the rapid current changes and, therefore, reduce the voltage spikes. Load reactors are suited for cable lengths less than 300 feet.
  • A dv/dt filter combines inductors, capacitors, and resistors to decrease voltage spikes and filter out fast transients from the circuit. They are more expensive than load reactors, but they provide much greater protection, generally allowing motors to be upwards of 1,000 feet away from the VFD (Figure 4).
  • Sinewave filters are the most expensive and complex output filter available for VFDs, but they provide the best protection. They essentially transform the output voltage into a clean sinusoidal waveform and can provide protection up to 15,000 feet. However, because of cost, they should only be considered for distances greater than 1,000 feet.

Joe Doughney, PE, is a CDM Smith electrical engineer, Raleigh, North Carolina; Levi Ambrose, EIT, is a CDM Smith electrical engineer, Fairfax, Virginia. Edited by Mark T. Hoske, editor-in-chief, Control Engineering, WTWH Media, [email protected].

Keywords

Variable frequency drives, VFD designs, VFD features, modern VFDs

Consider this

Are your VFDs using up-to-date technologies to deliver maximum benefits?

You also might like

Control Engineering has more industrial motors and drives knowledge.

Control Engineering has more mechatronics and motion control.

CDM Smith also wrote: Fit motor enclosures, protective sensors to the application

Written by

Joe Doughney, PE; Levi Ambrose, EIT, CDM Smith

Joe Doughney, PE, CDM Smith, Raleigh, North Carolina, is an electrical engineer with a focus on design and analysis of electrical power systems.

Levi Ambrose, EIT, CDM Smith, Fairfax, Virginia, is an electrical engineer with a focus on design and analysis of electrical power systems.