An affordable retrofit prevents expensive replacements

When a utility’s new SCADA system wouldn’t communicate with existing RTUs, replacements were planned, but there wasn’t much room in the budget. A growing customer base also stressed the need for building in expandability.

By Wesley Benefield October 8, 2013

The Harvest-Monrovia Water & Sewer Authority (HMWSA) was established in August 1965 to operate and maintain a water system to provide domestic water in the Harvest-Monrovia area of Madison County, located near Huntsville, Ala. In its early years, the utility serviced only 700 customers, but with growth in the area, HMWSA now serves a population of 42,000 inhabitants through 15,000 water meters.

In less than 50 years, the system has gone from only two wells providing 1.15 million gpd to today’s demands of 12 million gpd. To provide for this increase, HMWSA has grown to include two state-of-the-art water treatment plants manned by 41 employees. Although that represents exponential growth from the original two-person workforce, it’s still a relatively small number to cover the main plants and numerous remote sites (see Figure 1).

In July 2011, HMWSA received multiple awards from the Alabama Water Pollution Control Association:

  • Best Operated Plant Award for the 2 million gpd membrane package water treatment plant and the 10 million gpd water treatment plant
  • Excellence in Operation for three wastewater treatment plants
  • Best Operated Distribution System in Alabama in the 5,001-15,000 water meter category.

Expanding the system

In 2002, the authority’s board of directors decided it was time for the HMWSA to start providing sewer services to additional locations in the Harvest-Monrovia service area. As a result, it built two new wastewater treatment plants to handle the expansion. This greatly increased wastewater treatment capacity, which had previously consisted of two small treatment plants.

The four wastewater plants have a total capacity of 850,000 gpd. The Authority also administers sand filter-style treatment plants in 20 subdivisions. Overall, the water and wastewater system now comprises 44 remote sites, with plenty of bandwidth to add more sites for this rapidly growing area.

The lift stations and sand filters are spread out over a large area and must be monitored closely to avoid system disruptions or spills, but HMWSA only has a small maintenance crew of two to three people.

These changing demands created a need for a SCADA (supervisory control and data acquisition) system that could economically supervise the lift stations and other remote sites, so maintenance could be notified of an issue before a problem escalated.

To improve monitoring and control of remote sites in its wastewater system, HMWSA purchased and implemented a SCADA system from a major automation supplier. Unfortunately, the SCADA system wouldn’t function as required with the existing remote terminal units (RTUs), despite the fact that the RTUs had been previously purchased from that same supplier.

After a few years and a lot of expense, HMWSA was only able to get three sites online, and the data supplied to the SCADA system from the RTUs wasn’t meeting the needs of the utility. It didn’t want to replace the new SCADA system, but it needed to find another solution to improve operations, all while minimizing costs.

At this point, HMWSA approached our company, RTUdirect, based on our package of services and products, and large installed base among water and wastewater utilities. We studied the existing system and then suggested a retrofit that would build upon the existing SCADA and network systems.

Existing system issues

The SCADA system HMWSA installed uses canopy-style Ethernet radios to create a wide area network. This type of communications system is often used to provide wireless Ethernet connectivity and Internet service to communities in difficult-to-access and rural areas. The problem was that the existing RTUs were communicating with the central SCADA system via a polling-based with-exception reporting format. Polling-based systems don’t require a lot of bandwidth, but they also can’t provide the real-time data needed for a SCADA system to provide accurate and timely data.

With these polling-based RTUs, the central SCADA system polls each remote site once every 30 minutes. If an alarm or event occurs at a remote site, such as a pump coming on, the RTU will update the central SCADA system with an exception report, but this procedure lacks the immediacy of real-time data reporting required by the utility.

Due to these and other limitations, after two years the SCADA system had only eight RTUs connected with essentially no real-time monitoring or alarming capability.

Finding a low-cost solution

Our company demonstrated a solution to the utility via a pilot project. For the project, we created an RTU using a PLC and associated I/O with an Ethernet module. The Ethernet module was then connected to the existing network, providing a high-speed and reliable wireless Ethernet SCADA/RTU communication system.

This solution provided a low-cost method for acquiring data from remote sites, transmitting and receiving data from the central SCADA system, and controlling components and equipment at the remote sites—all in near real-time as required by the utility.

After the successful pilot project demonstration, the decision was made by HMWSA to replace the existing RTUs along with replacing a variety of existing control panels from different manufacturers that needed to be integrated into the SCADA system from various remote sites. The assorted panels were replaced with the same design throughout.

Although the new panel has a small footprint, in some instances we couldn’t fit it into existing spaces where the old panels had been installed at the remote sites. In these instances, we installed the PLC in a small fiberglass cabinet next to an existing panel, and wired the new PLC to existing controllers and components. The data could then be delivered in a uniform format to the SCADA system.

During the retrofit, HMWSA received approval to add new remote sites, which were each supplied with the new-design RTU, maintaining consistency with the RTU retrofits (see Figure 2).

In order to cover the entire geographic area of the water and wastewater system, we improved the canopy Ethernet system by installing a few towers with radios at key locations to complement radios already mounted on water tanks. We then reconfigured communication paths to improve network performance and make it easier to add new sites.

The HMWSA now has 44 sites online, with the capacity to add many more. The speed of the wireless canopy Ethernet network enables a real-time display of conditions in the system including motor amp readings, water pressure, dissolved oxygen levels, and other variables (Table 1). In addition, the SCADA system can be used to issue commands to the remote sites, controlling equipment as required to deal with issues and optimize operations.

Using real-time data to improve operations

After the retrofits and upgrades, a previously mismatched system became standardized and capable of providing important real-time data for monitoring and control such as number of starts, run time, and other important operating information (see Figure 3). 

The current SCADA system is a valuable asset for system managers to diagnose and adjust processes to achieve peak performance. The essential information needed for system maintenance and repair is now displayed in real time. If there’s a high level at a lift station, the SCADA system immediately receives this information, allowing operators to take action to correct the problem before a spill occurs.

Moreover, the SCADA system not only alerts operators of existing and imminent issues, it also allows qualified staff to spot problems before they occur and perform proactive maintenance. The system’s trending and analysis capabilities make it easy for operators to see where improvements in efficiencies can be made, and to improve overall operations.

In-depth analysis of data and operating condition has also helped HMWSA make better budget decisions for new equipment purchases, obviating the need to purchase and warehouse certain items of new equipment.

Keeping costs low

Because the HMWSA had already spent a considerable sum on its SCADA system, funds were limited to make the required upgrades and improvements. By making extensive use of simple and inexpensive components and by taking other actions to provide a low-cost solution, we were able to stay within the modest budget while still meeting performance and safety requirements.

By upgrading the canopy Ethernet system to provide the communications backbone of the system, and by replacing polled-based RTUs with new RTUs with improved communications capabilities, the HMWSA is now able to monitor even analog values in real time, all without having to spend a fortune replacing the existing SCADA and communications infrastructure. 

Furthermore, the retrofit and the new automation systems significantly improved the system by providing a real-time clock, high-speed and reliable Ethernet connectivity, and trending information that can be used to plan for improvements. Most importantly, the retrofitted and new automation systems help HMWSA provide better service to its customers.

Wesley Benefield is president of RTUdirect.

Key concepts:

  • Updates in control systems may not always be compatible with existing infrastructure.
  • RTUs can be built in-house using off-the-shelf components. 